AIR ADJUSTMENT Max Gas 170-250 P
B
A
To adjust air flow, turn the screw A as required. To redu-
ce output, turn screw clockwise, to increase it turn screw
counterclockwise. Note: screw B not used.
With the burner switched off, connect a DC microammeter with a 0÷50 or 0÷100 µA dial. When the burner is running,
and is properly adjusted, the value read must be steady and never be smaller than 3 µA(Landis).
AIR SERVOMOTOR ( SIEMENS SQN 75 ) MAX GAS 170-250 PAB
Remove cover to enter the adjusting cams. Adjust cams through the suitable key (on
issue) and a screwdriver.
I - Adjusting cam (BLUE) for air damper position on burner's shutdown
(total close 0°).
II - Adjusting cam (ORANGE) for opening position in ignition and Low Flame
(by the screwdriver).
III - Adjusting cam (RED) for opening position in High Flame (max. output).
IV - Adjusting cam (BLACK) to allow the opening of High flame solenoid valve.
FLAME DETECTION SYSTEM CHECK
min. 3 µA
pag.11
420010385801 M ax G as 170 - 250 P/ P AB
SETTING THE FIRING HEAD
1
ANDIS
GB 21 / GB 22