Displays
Pos.
Colour
MS
Green
(Module State)
EN
Yellow
(Enable)
ME
Red
(Module Error)
AS
Yellow
(Acknowledge
Stop)
BE
Red
(Bus Error)
DE
Red
(Drive Error)
Blinking: on/off every 0.5 s
EDK94AYAF DE/EN/FR/ES/IT 1.0
State
Description
On
Drive−based safety has initialised without a fault.
Drive−based safety has initialised without a fault.
Internal communication to the standard device is not
Blinking
possible.
Drive−based safety is in service status.
Flashing
For exiting, parameterise the drive−based safety.
Drive−based safety is not initialised.
Off
Acknowledgement is not possible.
On
Controller enabled
Off
Non−safe display "STO"
On
System error
Blinking
Trouble
Flashing
Warning
Off
Error−free operation
Request of an acknowledgement for the restart or the
On
parameter set adoption
Blinking
SS1/STO active
Flashing
SS2/SOS active
Off
No stop function active
Safety bus error:
l
On
Communication is not possible.
l
Acknowledgement is possible.
Blinking
Safety bus error: no valid configuration.
Off
Safety bus: error−free operation.
Drive−based safety is not accepted by the standard
device (see notes in the instructions for the standard
On
device).
Drive−based safety is correctly recognised by the
Off
standard device.
Flashing: on/off every 0.1/0.9 s
l