LEGRAND MP6-DMX3 Mode D'emploi page 66

Unité de protection
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

By pushing the "last trip"
the protection unit
The informations shown can be:
I>Ir: overload
I >Im: short circuit
I >Ii: instantaneous
I >Icw: instantaneous (fixed)
I >Ig: in case of earth fault
°C>T: overtemperature
Test: after test tripping
By pushing the "trips counter"
trip type
This page will show the number of occurred trips and the number of trips classified by
type:
- I>Ir: number of overload trips
- I>Im: number of short circuit trips
- I>Ii: number of instantaneous trips
- I>Icw: number of instantaneous (fixed) trips
- I>Ig: number of earth trips
- T>95°C: number of overtemperature trips
66
button it's possible to read the last trip cause saved by
it's possible to enter the following page:
total number
of trips