Max. Load Dependent On Ambient Temperature And Line Voltage - Helios FU Comfort Sinus Manuel De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification FU Comfort Sinus
Permissible rel. humidity
Electromagnetic compatibility for the
standard voltage 230 / 400 V accord-
ing to DIN IEC 60038
Harmonics current
Vibratory strength
(for vertical installation, i.e. cable inlet
down).
* Regarding the mains connection, these devices are to be classified as category "C2" devices according to the relevant
DIN EN 61800-3. The increased requirements placed on electrical interference > 2 kHz for category "C1" devices are
complied with in addition.
13.1.1

Max. load dependent on ambient temperature and line voltage.

The maximum permissible temperature for the rated current at rated voltage is specified as rated
temperature.
Since the dissipation of the power loss (heat development) in the device is decisively dependent on
the ambient temperature, the max. load must be reduced at an ambient temperature above the rated
temperature (see following table)!
The average value measured during a 24 h period must be 5 K under the max. ambient temperature.
For installation in a switch cabinet, the device's dissipation and its possible affect on the ambient
temperature must be taken into consideration!
Since the power loss in the device increases with rising line voltage, the following table must be
observed.
Type
FU-CS 2,5
FU-CS 8
FU-CS 10
FU-CS 14
FU-CS 18
FU-CS 22
FU-CS 32
FU-CS 40
FU-CS 50
L-BAL-E304-GB 2004
85 % no condensation
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
For devices < 4 A according EN 61000-3-2
For devices ≥ 4 A and ≤ 16A accorording EN 61000-3-2 (see Operating Instructions /
Electrical installation / harmonics current for devices ≥ 4 and ≤ 16 A)
For devices > 16 A and ≤ 75 A according to EN 61000-3-12 (see Electrical Installation /
Harmonics current and line impedance)
FU-CS 2,5...22
Broadband noise (simulated life-endurance test) in accordance with EN 61373, cat-
egory 1 class B.
Shock test according to EN 61373, category 1
Maximal load depending on line voltage and ambient temperature
208 V (-15 %)...415 V (+6 %)
40 °C
50 °C
55 °C
2,5 A
2,0 A
1,5 A
8,0 A
8,0 A
7.5 A
10,0 A
10,0 A
10,0 A
14.0 A
12.0 A
11,0 A
18,0 A
16.0 A
12.0 A
22,0 A
18,0 A
15,3 A
32.0 A
32.0 A
30.0 A
40,0 A
40,0 A
37,0 A
50,0 A
50,0 A
48,0 A
Part.-No.
120/139
over 415 V (+6 %)...480 V (+10 %)
40 °C
50 °C
2,2 A
1,5 A
8,0 A
8,0 A
10,0 A
10,0 A
14.0 A
12.0 A
18,0 A
15,0 A
22,0 A
17.0 A
32.0 A
32.0 A
40,0 A
40,0 A
50,0 A
50,0 A
Enclosure
55 °C
1,2 A
7,0 A
10,0 A
10,5 A
11,5 A
14.5 A
30.0 A
35,0 A
46.0 A

Publicité