G
®
PREMASGARD
The pressure measuring transducer PREMASGARD
into standard signals of 0 -10 V or 4...20 mA. Process connection is G ½ " straight external pipe thread. SHD-SD is used for pressure measurement
in gaseous and liquid media. Applications of this pressure transmitter are in hydraulics, pneumatics, process technology, in mechanical and plant
engineering. Not applicable for ammonia and Freon!
TECHNICAL DATA
Power supply:
Measuring ranges:
Output signal:
Electrical connection:
Pressure connection:
Type of pressure:
Measuring principle:
Temperature of medium:
Mounting:
Enclosure:
Connecting head:
Medium contacting parts:
Response time:
Load changes:
Characteristic line:
Overload range/
Bursting pressure:
Protection class:
Protection type:
Standards:
Optional:
ACCESSORIES
Connecting diagram
2
Output pressure 0-10V
3
GND
1
Supply voltage
UB+ 24V AC/DC
®
PREMASGARD
SHD - SD – Pressure measuring transducers, Standard
Type ⁄
Measuring
WG01
Range
SHD - SD - U
S H D - S D - U 6
0...6 bar
S H D - S D - U 10
0...10 bar
S H D - S D - U 16
0...16 bar
SHD - SD
®
SHD-SD measures relative pressures in the bar range. It converts the measurand pressure
24 V AC ⁄ DC for output 0 -10 V
7 - 33 V DC for output 4 ... 20 mA
see table
(other ranges upon request)
0 -10 V, 3-wire, (working resistance > 10 kOhm) or
4... 20 mA, 2-wire, (working resistance < (UB (V) -7 V) ⁄ 0,02 A ;
R
depending on working resistance
L
plug connector DIN EN 175301-803-A
G ½ " sealing at the back, and manometer (combined) with profile gasket FPM,
special WW G ¼ " DIN 3852
relative
ceramic measuring cell
–15...+ 125 °C
directly on pressure line
stainless steel 1.4305
plastic, approx. 98 x 50 x 34 mm
stainless steel type 1.4305, AISI 303;
measuring element ceramic Al
sealing material FPM (Viton)
2 ms (1 ms typical)
< 100 Hz
± 0.3 %
< 4 bar: 3 x FS
> 4 bar: 2.5 x FS
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
Display module, additional height: approx. 50 mm, for displaying the pressure
incl. receptacle DIN EN 175301-803-A
SHD - SD - U
OUT
2
3
1
+
IN
Item No.
U - variant
13 01 - 2121- 0550- 120
13 01 - 21 21- 0560- 120
1 30 1 -2 12 1-0570 -120
0
(96%);
2
3
Connecting diagram
2
Output pressure 4...20mA
GND
3
Free
1
Supply voltage
UB+ 24V DC
Type ⁄
WG01
SHD - SD - I
S H D - S D - I 6
S H D - S D - I 10
S H D - S D - I 16
OUT
2
3
1
+
IN
Measuring
Item No.
Range
I - variant
0...6 bar
1301-2122-05 50-000
0...10 bar
1301-2122-0560 -000
0...16 bar
1301-2122-0570-000
Rev. 2018 - V13 GB
SHD - SD - I