YOKOGAWA Vigilantplant EXAxt SC450 Manuel D'instructions page 34

Transmetteur de conductivité ou de résistivité
Table des Matières

Publicité

Control
Alarm
Hold
USP
Fail
Simulate
Off
Menu
PID-control S1
PID-control S1
PID-control S1
PID-control S1
PID-control S1
Duty cycle
Pulse freq.
mA1 (simulate)
Alarm S1
Alarm S2
Alarm S1
Alarm S1
Alarm S1
Hold
Hold
Paramètre
Valeurs
par défaut
Setpoint
250.0 µS/cm
Range
50.0 µS/cm
Manual Reset
0%
I-time
3600 s
D-time
0 s
DC period time
10 s
Max. pulse freq.
70 p/min
Expire time
0.0 s
Setpoint
450.0 µS/cm (high)
Setpoint
50.0 µS/cm (low)
Hysteresis
4.500 µS/cm
Delay Time
0.2 s
Expire Time
0.0. s
Fixed value mA1
12 mA
Fixed value mA2
12 mA
Setpoint
Range
(proportional)
Direction
I-time
S2, S3, S4 semblable à S1
min.
- inf
- inf
0%
1 s
0 s
1 s
1 p/m
0 s
- inf
- inf
0 mS/cm
0 s
0 s
3.6 mA
3.6 mA
PI-control S1
250.0μS/cm
50.00μS/cm
Reverse
3600 s
Enter
Etendue
max.
+ inf
+ inf
100%
3600 s
60 s
1800 s
120 p/m
1800 s
+ inf
+ inf
+ inf
+ inf
1800 s
21 mA
21 mA
IM 12D08N05-01F-E