Venting Application Flow Chart; Horizontal Termination; Vertical Termination; Definitions - Napoleon Fireplaces BL36NTE Instructions D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

14
3.5

VENTING APPLICATION FLOW CHART

EN

Horizontal Termination

Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
3.6

DEFINITIONS

For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
H
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
T
H
- combined horizontal vent lengths in feet
R
H
- offset factor: .03 (total degrees of offset - 90°*) in feet
O
V
- combined vertical vent lengths in feet
T
3.7

ELBOW VENT LENGTH VALUES

FEET
0.03
15°
0.45
30°
0.9
45°
1.35
90°*
2.7
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
W415-1442 / D / 12.01.16
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 24.75
feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
INCHES
MILLIMETERS
0.5
12.7
6.0
152.4
11.0
279.4
16.0
406.4
32.0
812.8
TOP EXIT

Vertical Termination

Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
35 feet (10.7m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.3A
14.1
15.1A

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Bl36pte

Table des Matières