Télécharger Imprimer la page

Siemens MICROMASTER 440 Guide Rapide page 12

Masquer les pouces Voir aussi pour MICROMASTER 440:

Publicité

P0311*
Rated Motor Speed
0 – 40000
Nominal motor speed (rpm) from rating
1/min
plate
P0700
Selection of Command Source
(on / off / reverse)
1 = BOP
2 = Terminal / Digital Inputs (default)
P1000
Selection of Frequency Setpoint
1 = BOP
2 = Analogue Setpoint (default)
P1080
Min. Motor Frequency
Sets minimum motor frequency
(0-650Hz) at which the motor will run
irrespective of the frequency setpoint.
The value set here is valid for both
clockwise and anti-clockwise rotation
P1082
Max. Motor Frequency
Sets maximum motor frequency (0-
650Hz) at which the motor will run at
irrespective of the frequency setpoint.
The value set here is valid for both
clockwise and anti-clockwise rotation
12
English
Deutsch
Motornenndrehzahl
Motornenndrehzahl (1/min) aus dem
Typenschild
Wahl von Befehlsquellen
(EIN / AUS / Richtungsumkehr)
1 = BOP
2 = Klemmen (Werkseinstellung)
Wahl des Frequenzsollwerts
1 = BOP
2 = Analogsollwert (Werkseinstellung)
Min. Motorfrequenz
Stellt die minimale Motorfrequenz
(0-650Hz) ein, mit der der Motor unabhän-
gig vom Frequenzsollwert läuft. Der hier
eingestellte Wert gilt für beide
Drehrichtungen
Max. Motorfrequenz
Stellt die höchste Motorfrequenz (0-
650Hz) ein, mit der der Motor unabhängig
vom Frequenzsollwert läuft. Der hier
eingestellte Wert gilt für beide
Drehrichtungen

Publicité