ETA Systems
®
- SECURITY ONE UNINTERRUPTIBLE POWER MANAGER
International Electrical Ratings
VA/Watts
Frequency (Hz.)
420/294
50/60
600/420
50/60
800/560
50/60
1100/770
50/60
1440/1008
50/60
Energy Consumption
VA Rating
Efficiency
420 VA
92%
600 VA
93%
800 VA
93%
1100 VA
94%
1440 VA
94%
General Electrical
Voltage waveform on AC line – Sine wave (conditioned AC main)
Voltage waveform on inverter (backup mode) – Sine wave (conditioned inverter)
Transfer time (includes detect time) – 4 ms. typical
Input frequency (AC mode) – North American Models: 57 – 63 Hz.
International Models: 47 – 53 Hz.
Output frequency – AC mode: Follows Input
Inverter mode: 50 Hz or 60 Hz. + 0.1 Hz.
(determined by power line frequency prior to outage)
THD (inverter mode) – <3%
Minimum backup time full load/half load – 6 min./20 min.
Efficiency (on main) - 92% or higher
Rated Voltage
Max. Output – Amps@230VAC
220/230/240
1.8
220/230/240
2.6
220/230/240
3.5
220/230/240
4.8
220/230/240
6.3
Output BTU/Hr.
115
143
200
225
250
94