Télécharger Imprimer la page

Outdoor Unit; Part 1: General; Part 2: Installation; Part 3: Components - Haier Arctic Série Manuel D'utilisation/De Spécifications

Masquer les pouces Voir aussi pour Arctic Série:

Publicité

Les langues disponibles

Les langues disponibles

OUTDOOR UNIT

Part 1: General

1.1 Outdoor Unit
A. The Haier Arctic outdoor unit shall be comprised of a condenser coil with all components and controls
necessary to perform the rated operation.
1.2 Warranty
A. The outdoor unit shall be covered by a manufacturer's parts warranty. See Appendix for details.
1.3 Sound Pressure Rating

Part 2: Installation

2.1 Condensate
A. The installer must adhere to local building codes for managing condensate water produced by the outdoor unit.
2.2 Clearances
A. The installer must follow the recommended clearances provided in the Installation Manual.

Part 3: Components

3.1 Coil
A. The outdoor coil shall be made with a blue colored hydrophilic coating on the aluminum fins and packed with internally
shorter defrost cycles (approx. 29%.)
B. Coils shall be helium pressure tested at the factory within a range of 600 - 650 PSI.
C. Outdoor unit shall be factory charged with R-410A refrigerant for 100 feet of lineset.
3.2 Fan Motor
A. The outdoor fan motor shall be a brushless, variable speed DCV motor type.
B. The fan motor shall be molded with heat-hardened resin.
C. The fan motor shall have permanently lubricated SRC bearings.
3.3 Fan Blade
A. The outdoor fan blade shall be a UL flame rated plastic-resin design.
B. The fan blade shall be factory balanced in quiet performance and enhanced velocity.
3.4 Compressor
A. The compressor shall be a DC rotary type and A-PAM inverter-driven for stable operation in lower and higher
frequency.
B. The compressor shall be vairable speed, variable capacity.
C. The compressor shall have an internal overload protection device.
D. The compressor shall use PVE (FV50S) refrigerant oil for better anti-wear effectiveness, superior resistance to
capillary tube blockage and no hydrolysis compared to POE oil.
3.5 4WV
A. The outdoor unit shall contain a four-way reversing valve (4WV) to change system mode from cool to heat.
3.6 EEV
A. The refrigerant flow shall be regulated by an electronic expansion valve (EEV).
B. The outdoor control shall monitor the refrigerant flow through the EEV using a pulse-operated coil.
C. The EEV shall maintain the target of 10°F (5.5°C) of superheat.
3.7 Base Pan
A. The outdoor unit shall have a galvanized steel base pan.
B. The base pan shall have multiple drain holes located under the coil and throughout the pan to provide efficient
draining of defrost discharge and to prevent accumulation of damaging ice.
3.8 Pan Heater
A. The base pan of the outdoor unit shall contain a tubular electric heater to prevent condensate water from freezing.
B. The pan heater shall be enabled and operated by software when the ambient is below 37°F (3°C).
C. The pan heater shall be protected with a thermal cut-out.
12
Model
Sound Pressure
Rating dB (A)
2U20EH2VHA
56
3U24EH2VHA
56
31-5000410 Rev. 0

Publicité

loading