INSTRUCTION
EN
OPTIGO OP5U
i
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this symbol
is used, in order to find out the nature of the potential
hazards and any actions to be taken
Controller with display
Optigo OP5U is a pre-programmed, configurable controller. It has 5
inputs/outputs and can be configured to control temperature, CO
humidity or pressure. All configuration and normal handling is done
using the display and the knob on the front. From revision R18, it is
possible to connect an external PT1000 setpoint device.
Technical data
Supply voltage
24 V AC ±15%, 50/60 Hz
Power consumption
3 VA
Ambient temperature
0...50°C
Ambient humidity
Max. 90% RH
Storage temperature
-20...70°C
Display
Numeric / graphic. Background
illumination.
Inputs/outputs
Refer to connection illustrations and
table below
Terminal blocks
Disconnectable, so-called lift type for
cable cross-section max 2.5 mm
Protection class
IP20
Material, casing
Polycarbonate, PC
Weight
215 g incl. terminal blocks
Dimensions
122 x 120 x 64 mm (WxHxD incl. terminals,
fixed installation)
Pollution degree
2
Temperature settings
Temperature, supply air
-20..+60, 20...100, 60...140°C
Setpoints
-18...+60, 22...100, 62...140°C
External setpoint
0...40°C
Neutral zone
0...10°C
P-band
0...99°C
I-time
0...990 s
Min. limit damper
0...99
Other settings
Setpoint values
CO
0...100% of max set value on UI1
2
General (GEN)
0...100% of max set value on UI1
Pressure (Pa)
0...100% of max set value on UI1
Scaling of UI1
0...10 V DC in
CO
10...9900 ppm
2
General
0...100%
Pressure
100 Pa...2500 kPa
Neutral zone
12.5% of max
P-band
CO
0...100% of UI1
2
General (RH)
0...100% of UI1
,
Pressure (Pa)
0...300% of UI1
2
I-time
0...990 s
Control setting 5
Outdoor compens. start
-20...+60°C
Setpoint pressure at
-20°C outdoor temp.
0 Pa...2500 kPa
OPTIGO OP5U
Installation
OP5U must be mounted in a DIN-standard casing (minimum 7
modules) or in a cabinet, either on a DIN-rail or, using the two screw-
2
pockets provided, by being screwed to any suitable flat surface in the
cabinet. The controller can also be mounted in a cabinet door or other
control panel, using a suitable front-mounting kit.
The controller must be connected to a 24 V AC safety insulating
transformer providing mains insulation.
Follow table 1 below for connection.
Table 1. I/O connection terminals. Terminals 2, 20 and 50 are internally con-
nected.
Terminal
Designation
1
G
2
G0
3
20
AGnd
21
AO1
22
AO2
41
DI+
42
DI1
43
UI+
44
UI1
50
AGnd
51
AI1
52
SPI
Digital inputs DI and UI are only intended to be used with
a potential-free contact or switch. If the Optigo OP5U and active
sensors and actuators connected to it share transformer, it is
essential that the same transformer-pole is used as reference for
all the equipment. Failure to do so will prevent the equipment from
functioning as intended and may also lead to damages.
For best protection against disturbances, a shielded twisted-pair cable
should be used for wiring the sensors. Ground the shield at one end.
The protection provided by the equipment may be impaired by im-
proper use.
Operation
Supply voltage 24 V AC
Ref. for AO1 and AO2
0...10 V DC Output
0...10 V DC Output
Reference for DI1
Digital input
Reference for UI1 digital mode
0...10 V DC or Digital input
Ref. for AI1 and UI1 analogue
PT1000 temp. sensor input
Input PT1000 setpoint device
1

Publicité

Table des Matières
loading

Sommaire des Matières pour Regin OPTIGO OP5U

  • Page 1 Optigo OP5U is a pre-programmed, configurable controller. It has 5 General (RH) 0...100% of UI1 a potential-free contact or switch. If the Optigo OP5U and active inputs/outputs and can be configured to control temperature, CO Pressure (Pa) 0...300% of UI1 sensors and actuators connected to it share transformer, it is humidity or pressure.
  • Page 2: Control Modes

    Min. setpoint= -18, max.= +60 tion. Pressure Frequency Medium (2) 20...100°C Min. setpoint= 22, max.= 100 transmitter converter High (3) 60...140°C Min. setpoint= 62,max.= 140 AO1 inverted signal °C Outdoor temp sensor Figure 5. Wiring example: Outdoor temperature compensated pressure control. OPTIGO OP5U...
  • Page 3: External Setpoint

    Note: The controller must display the Base Display when pressing the sation See the “Optigo OP5U Manual” for more information about the encoder knob to reach the 10-second level. configuration menus in the 10-second level. The manual can be downloaded from www.regincontrols.com.
  • Page 4 The calculated setpoint is dis- played by turning the knob clockwise when in the Base Display. Optigo OP5U är en förprogrammerad, konfigurerbar regulator. Den har 5 ingångar/utgångar och kan konfigureras till att styra temperatur, , fukt eller tryck. All konfigurering och normal hantering görs via displayen och ratten på...
  • Page 5 TG-R4/ Neutralzon 12,5% av max PT1000 kontakter. Om Optigo OP5U och de aktiva givare och ställdon som kopplas till den P-band Figur 1. Inkopplingsexempel: Värme/kyla med change-over-funktion delar transformator, är det nödvändigt att samma transformatorpol an- och extern börvärdesomställare. 0...100% av UI1 Generell (GEN) 0...100% av UI1...
  • Page 6 (-20...+60°C). Ur AO2 fås den inverterade signalen av genom att vrida ratten då symbolen “Menyn innehåller ändringsbara AO1. P-band P-band P-band P-band P-band värden” ( ) inte blinkar. I vissa fall leder ett val i en meny till att man bara ser vissa andra menyer. OPTIGO OP5U...
  • Page 7: Teknisk Support

    Beräknat börvärde: I reglerfall 5, Tryckreglering med utetemperatur- kompensering, arbetar regulatorn inte mot det inställda börvärdet utan Se “Optigo OP5U Manual” för mer information om konfigurerings- menyerna i 10-sekundersnivån. Manualen kan laddas ner från mot ett beräknat börvärde som är beroende av utetemperaturen. Genom att vrida ratten medurs när man befinner sig i Grunddisplayen visas det...
  • Page 8: Régulateur Avec Écran

    Régulateur avec écran Les entrées digitales DI et UI ne doivent être raccordées qu’à 0...100% de UI1 des contacts libres de potentiel. Si l’Optigo OP5U, les sondes et Général (HR) 0...100% de UI1 autres organes de commande associés (actionneurs) sont alimentés Optigo OP5U est un régulateur préprogrammé...
  • Page 9 Le point de consigne au niveau de la sonde est rétabli en bas (-20...+60°C). Le signal AO1 inversé est reçu de AO2. régulant le signal des sorties AO1 et AO2. AO1 est utilisé pour la régulation positive, AO2 pour la régulation négative. Une seule OPTIGO OP5U...
  • Page 10: Consigne Externe

    OFF pour un point de consigne interne. Avec le point de consigne externe, vous ne pouvez voir la valeur actuelle de la con- Voir le manuel «Optigo OP5U - Manuel» pour en savoir plus sur les signe que dans le menu de réglage des consignes. Lorsqu’un appa- menus de configuration.
  • Page 11 Regler mit Display Universal (GEN) 0...100% von UI1 Symboles utilisés pour l’affichage Druck (Pa) 0...300% von UI1 Optigo OP5U ist ein vorprogrammierter, konfigurierbarer Regler. Er ver- I-Zeit 0…990 s Compensation Change-over fügt über 5 Ein-/Ausgänge und kann so konfiguriert werden, dass er Numéro de menu...
  • Page 12 Die digitalen Eingänge und UI sind nur für die Verwendung Start- mit einem potentialfreien Kontakte oder Schalter vorgesehen. signal °C Werden der Optigo OP5U und die angeschlossenen aktiven Fühler Befeuchter und Stellantriebe vom gleichen Transformator gespeist, muss als % RF Bezugsmasse immer der gleiche Transformatorpol für die gesamte...
  • Page 13 Aufrufen des Konfigurationsmenüs. Regler bei Drücken den Drehknopfs das Basismenüdisplay anzeigen. temperatur- kompensation Für weitere Informationen über das Konfigurationsmenü im 10-Sekunden-Menü, siehe das “Optigo OP5U Handbuch”. Das Hand- buch kann unter www.regincontrols.de heruntergeladen werden. Maximale Kompensation Das Basismenü Tabelle 2 unten zeigt die Anordnung des 10-Sekunden-Menüs. Wenn Falls keine Eingaben erfolgen, wird das Basisdisplay angezeigt.
  • Page 14 Der externe oder interne Sollwert wird durch Einstellung von Kontakt EXT SP auf EIN (extern) oder AUS (intern) im Menü 1.E festgelegt. Regin Controls Deutschland GmbH, Bei Verwendung eines externen Sollwertgebers wird nur der aktuelle Haynauer Str. 49, 12249 Berlin, Deutschland, Sollwert im Sollwert-Menü...

Table des Matières