Control Modes - Regin OPTIGO OP5U Mode D'emploi

Masquer les pouces Voir aussi pour OPTIGO OP5U:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Control modes

Optigo can be configured to any one of the following control modes:
1.
Temperature control
The temperature at the sensor is kept at the setpoint value by
controlling the output signals on AO1 and AO2. The setpoint can
be set directly from the display or via an external setpoint device.
A single PI control loop is used.
The analogue outputs can be configured to the following combi-
nations:
AO1
AO2
Display symbols
1
Heating
-
\
2
Cooling
-
/
3
Heating
Cooling
\ /
4
Heating
Heating
\ \
5
Cooling
Cooling
/ /
6
Heating
Damper
\ /
7
Cooling
Damper
\ /
8
Change-over
-
G
1
G0
2
3
DI+
41
Start signal
DI1
42
UI+
43
G0
UI1
44
-
G
20
A
GND
°C
Y
21
AO1
A
50
GND
22
-
AI1
51
SPI
52
3
TG-R4/
4
PT1000
Figure 1. Wiring example: Heating/cooling with change-over function
and external setpoint device.
Level 1.6 of the menu is used for selecting the temperature operating
range. Here, it is possible to select:
Low (1)
-20...+60°C
Min. setpoint= -18, max.= +60
Medium (2)
20...100°C
Min. setpoint= 22, max.= 100
High (3)
60...140°C
Min. setpoint= 62,max.= 140
2.
CO
control
2
The CO
controlling the output signal on AO1. A single PI control loop is used.
Min./max. limitation of the output is possible.
Damper
Frequency
converter
Figure 2. Wiring example: CO
converter.
3.
General control
The setpoint at the sensor is returned by controlling the output
24 V AC
signals on AO1 and AO2. AO1 is used for positive control, AO2 for
negative control. A single PI control loop is used.
If you want to max. limit the humidity, connect a HMH humidistat in
+
series with the start signal to terminals 41 and 42.
Humidifier
Dehumidifier
Figure 3. Application example: Combined humidification/dehumidifica-
tion.
-value at the sensor is kept at the setpoint value by
2
G
1
24 V AC
2
G0
Start
3
signal
DI+
41
G0
DI1
42
G
CO
UI+
43
Y
UI1
44
G0
20
A
G
GND
21
AO1
A
50
S
GND
22
AO2
AI1
51
52
SPI
-
20
A
GND
+
21
AO1
22
AO2
control using damper or frequency
2
G
1
24 V AC
G0
2
3
Start
signal
DI+
41
DI1
42
-
UI+
43
+
UI1
44
G0
20
A
GND
-
21
AO1
A
50
GND
22
AO2
51
+
AI1
HMH Max limiting
SPI
52
humidistat
OPTIGO OP5U
Positive control,
direct-acting
AO1
Above graph drawn as during pure P control
4.
Pressure control
transmitter
2
The pressure at the sensor is kept at the setpoint value by
controlling the output signal on AO1. A single PI control loop is
0...10V
used. The AO1 inverted signal is recieved from AO2.
-
Frequency
converter
+
AO1 inverted signal
Figure 4. Wiring example: Pressure control.
5.
Pressure control with outdoor compensation
The pressure at the sensor is kept at the setpoint value by
controlling the output signal on AO1. The setpoint is automati-
cally adjusted according to the outdoor temperature. A single PI
control loop is used. When this control mode is used, the
temperature range is adjusted down to the low setting
(-20...+60°C). The AO1 inverted signal is recieved from AO2.
% RH
Humidity
transmitter
G
S 0...10V
-
Frequency
converter
+
AO1 inverted signal
Figure 5. Wiring example: Outdoor temperature compensated pressure
control.
Negative control,
reverse-acting
NZ
AO2
Temp. (°C)
Setpoint
G
1
24 V AC
G0
2
3
Start
signal
DI+
41
DI1
42
Pa
43
UI+
UI1
44
G0
Pressure
20
A
G
GND
transmitter
21
AO1
A
50
Y
GND
22
AO2
AI1
51
SPI
52
G
1
24 V AC
G0
2
3
Start
signal
DI+
41
DI1
42
Pa
UI+
43
44
G0
UI1
Pressure
20
A
G
GND
transmitter
21
AO1
A
50
Y
GND
22
AO2
AI1
51
°C
Outdoor temp
SPI
52
sensor
2

Publicité

Table des Matières
loading

Table des Matières