Nemo 72 Le
Programming
Menu is divided on two levels, protected by two different numerical passwords.
Programming is carried out by
front 3-key touch screen keyboard
U
I
P E .
Level 1
Password = 1000
1.0
Password
1.1
Customized display page
1.2
Connection
1.3
Current delay time and average power
1.4
Display lighting
1.5
Run hour meter count start
1.6
RS485 ModBus RTU/TCP or BACNET communication
1.7
Relay output function: Energy pulses, Alarm, State of relay switching
(remote-controlled)
Level 2
Password = 2001
2.0
Password
2.1
External CT and VT ratio
4
Moves the cursor
In the pages with choice among the fixed values, it scrolls the
loadable values
Increases the loaded value
In the pages with choice among the fixed values, it scrolls the
loadable values
Confirms
During programming
I
+
by keeping pressed
keys
return to the previous page
U
+
by keeping pressed
keys
leave the programming menu, without save
nothing
Programmable Parameters
Level 1
1.1 Customized display page
Possibility to load a customized display page on which you can choose which quantities
the three display lines must show.
If the user loads a customized page, this will become the standard display when the
meter is switched on
The selectable displays for the customized page are mentioned in the tables page 7.
1.2 Connection
The meter can be used for single phase or three phase 3- and 4-wire network.
The selectable connections are:
Symbol
1N1E
3-1E
P E .
you
3N1E
3-2E
P E .
3-3E
you
3N3E
1.3 Current delay time and average power
Selectable delay time: 5, 8, 10, 15, 20, 30, 60 minutes
The selected time is valid both for the current and the average power
1.4 Display lighting
The 4 selectable levels (0 – 35 – 70 – 100%) show the display lighting percentage
1.5 Run hour meter count start
Select the quantity which starts the run hour meter count: voltage or power.
Voltage: count start with phase voltage > 20V
Power: total active power, programmable value 0,5...50%Pn (rated power)
1.6 RS485 communication
According to the models, this meter can be without communication or equipped with
RS485 ModBus RTU/TCP or RS485 BACNET communication
1.6a RS485 ModBus RTU/TCP communication
Address number: 1...255
Parity bit: none – even – odd
Waiting time before answer: 3...100ms
Transmission speed: 4800 – 9600 – 19200 – 38400 bit/s
ModBus message word format
1
Just for 32-bit quantities
Password = 1000
(as alternative the one showing the line voltages)
Line
Load
Coils
Sigle-phase
-
1
3-phase 3 wires
Balanced
1
3-phase 4 wires
Balanced
1
3-phase 3 wires
Unbalanced
2
3-phase 3 wires
Unbalanced
3
3-phase 4 wires
Unbalanced
3
(where provided)
1
: Big Endian – Little Endian – Swap
.
Wiring
Connection
S 1000/251
S 1000/447
S 1000/448
S 1000/166
Aron L1 - L3
S 1000/446
S 1000/164
02/18 E02 10783332 WEB E cod.MF72...