Auxiliary Supply; Factory Settings - IME Nemo D4-e Manuel D'installation

Masquer les pouces Voir aussi pour Nemo D4-e:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Auxiliary Supply

Terminals 20 and 21
Auxiliary Supply: electrical power supply in AC or DC necessary for correct device
operation.
Check that the power supply voltage available corresponds to the one indicated on the
instrument data plate
(voltage value and possible frequency)
Where a double voltage is indicated
supplied with alternating current 80...265Vac or direct current 100...300Vdc. 20+ and 21-.
OUTPUT
INPUT
VOLTAGE
CURRENT
15 29
2 5 8
11
1
3
4
6
7
9
07/17 10783591 WEB E cod.MFD4E06
.
the instrument can be
(e.g. 80...265Vac / 100...300Vdc)
OUTPUT
AUX.
RS 485
SUPPLY
F : 0,5A gG
+
0V
+
33 34 35
20
21
F

Factory Settings

Password
1000
Customised page
Lin1v Voltage L1
1
2
Lin2v Voltage L2
Lin3v Voltage L3
3
Connection:
3n3E line 4 wires 3 systems
Average time:
15m 15 minutes
Hour-meter counting:
U Voltage start
RS485
Address: 255
Speed: 9.600
Parity: none
Transmission delay: 15msec
Pulse output
Energy: active
Pulse weight: 0,01kWh
Pulse duration: 50ms
Password
2001
CT ratio:
0001
Nemo D4-e
15

Publicité

Chapitres

Table des Matières
loading

Table des Matières