Télécharger Imprimer la page

Eaton DXC-EXT-2RO Mode D'emploi page 2

Publicité

L1 /L L2 /N
L3
1
2
3
4
5 6
7
8
9 10 11
U
V
W
2
mm
AWG
mm
0.14 - 1.5
30 - 16
7
DXC-EXT-2RO
1
+24 V OUT, < 100 mA
2
DI1: 4...+30 V = H, 0...+3 V = L, Ri ∼ 72 kΩ, Enable
3
DI2: 4...+30 V = H, 0...+3 V = L, Ri ∼ 72 kΩ, FWD/REV
4
DI3: 4...+30 V = H, 0...+3 V = L, Ri ∼ 72 kΩ, AI/FF1
5
+10 V OUT, < 10 mA
6
AI: 0...+10 V , < 20 mA, f-Soll
7
0 V
8
Relay K2 (NO): 250 V AC / 220 V DC, 1 A
9
Relay K2 (NO): 250 V AC / 220 V DC, 1 A
10
Relay K1 (NO): 250 V AC / 220 V DC, 1 A
11
Relay K1 (NO): 250 V AC / 220 V DC, 1 A
Relay K1 (NO)
P18 = 0
Enable
P18 = 1
RUN
P18 = 2
f-Motor = f-Soll
P18 = 3
Fault (Trip)
P18 = 4
f-Motor ≧ P-19
P18 = 5
l-Motor ≧ P-19
P18 = 6
f-Motor < P-19
P18 = 7
l-Motor < P-19
DC1
1
2
3
4
1
2
3
4
2/2
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
© 2012 by Eaton Industries GmbH,
www.eaton.com/moeller/support
1 2 3 4 5 6 7 8 9 10 11
1
2
3
4
5
6
7
8
9
10 11
M2.5
in
Nm
ft-lbs
0.27
0.5
0.37
Relay K2 (NO)
P25 = 0
P25 = 1
P25 = 2
P25 = 3
P25 = 4
P25 = 5
P25 = 6
P25 = 7
P-25
5
6
7
8
5
6
7
8
K2
f-Soll
4.7 kΩ
Emergency On Call Service: Local representative (www.eaton.com/moeller/aftersales) or +49 (0) 180 5 223822 (de, en)
mm
0.6 x 3.5
DC1...
1
2
3
4
5
6
7
8
9
RUN
10
RUN
11
Enable
RUN
f-Motor = f-Soll
Fault (Trip)
f-Motor ≧ P-19
l-Motor ≧ P-19
f-Motor < P-19
l-Motor < P-19
P-18 = 1
RUN
9
10
11
9
10
11
K1
250 V AC
220 V DC
≦ 1 A
All Rights Reserved
P-25
P-25
P18 = 1
P18 = 1
10/12 IL04012015Z
Printed in the UK (11/12)
DHW

Publicité

loading