Installation Instructions

Capacity Adjustments Instructions for Connect Series

AUH2436ZGDA Default capacity setting of outdoor unit is 36K, AUH4860ZGDA Default capacity setting of outdoor unit
is 60K. Installer will need to change dip switch to 24k when pairing with a 24 indoor AHU OR dip switch to 48K when
pairing with a 48K indoor AHU. Operation Instruction is below:
1. Dip switch settings must be completed before power on the unit.
2. Capacity dip switch is indicated by the red circle below.
Main control Board
Model Number
AUH2436ZGDA
AUH4860ZGDA
31-5000483 Rev. 3
Capacity Dip Switch
Dip Switch Configuration
Tonnage
36k (default)
24k
60k (default)
48k
1
2
3
ON
ON
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
4
OFF
OFF
OFF
OFF