Installation Instructions

Electrical Requirements

Control Wiring

Using 18 Gauge Solid Core Copper Wire
1. Cut back the insulation 1" from the end of the wire.
2. Remove the screw from the terminal block, and wrap
the wire around the screw.
3. Return the screw and wire to the terminal block and
tighten securely.
Stranded Wire
1. Cut back the insulation 3/8" from the end of the wire.
2. Make sure the round or forked terminal connector is
rated for the amperage of the unit being installed.
3. Use a crimping tool only to fasten the connector to the
wire.
4. Return the screw and connector to the terminal block
and tighten securely.
Solderless
Terminal
16

Electrical Connection

Model
Power Supply
AUH2436ZGDA 208/230V-1Ph-60Hz
AUH4860ZGDA 208/230V-0Ph-60Hz
Jacket / Insulation
Recommended breaker
size (A)
35
45

Wiring Connections

1. High and low voltage wires should be led through
different rubber rings of the electric box cover.
2. High and low voltage wires should be secured
separately. Secure the former ones with large clamps
and the latter ones with small clamps.
3. Use screws to tighten high and low voltage wiring on
the terminal board. Improper connection may create a
fire hazard.
4. Ground the units by connecting the ground wire.
5. All wiring must comply with local and national code.
Screw with
Special Fastener
Round
Terminal
How to Remove or Reinstall the Electric
Box Cover:
Remove the electric box cover :
1. First remove the top cover screws and move upward to
remove the top cover.
2. Then remove the screws of the maintenance cover,
push down the cover by hand until the tabs of the cover
move to the bottom of the slot, and then remove the
cover;
3. Put back the electric box cover:
4. First align the four tabs with the corresponding slots,
and then force push up, when all the claws are pushed
to the top of the slot, install the screws.
5. Then install the top cover, align the four corners and
press down until the top cover falls to the specified
position, and finally install the screws.
Terminal
Board
Wire