7.3

Setting maximum CH power

The maximum CH power is set to 60% in the factory. If more power is required for the
CH installation, the maximum CH power can be changed by adjusting the rpm of the
fan. See table: Setting CH power.
This table shows the relation between the rpm of the fan and the unit power.
Desired CH power in kW (approx.)
RKOMBG*AAV1
22
28
22.7
28.4
20.5
25.6
18.2
22.9
16.0
20.1
13.7
17.4
11.5
14.6
9.3
11.8
5.9
7.7
Caution:
The power is slowly increased when the fire is lit and is lowered when the set leaving
water temperature is reached (modulation on Tsupply).
The minimum feedthrough amount (l/h)
155
240
510
750
7.4

Set pump capacity

The RKOMBG*AAV1 CH boilers are fitted with a modulating A-class pump which
modulates on the basis to the CH power provided. The minimum and maximum
capacity of the pump can be adjusted with the parameters 3 and c. Also see par. 7.2.
The set value of parameter 3. (max. pump setting) is the percentage of the maximum
pump capacity and is linked to the set maximum CH power as set with parameter 3
The set value of parameter c. (min. pump setting) is linked to the minimum CH-power
as set with parameter c
If the CH load modulates between the minimum and maximum value, the pump
capacity will modulate along proportionately.
Pressure loss graph unit CH side
A.
RKOMBG22AAV1
B.
RKOMBG28AAV1
C.
RKOMBG33AAV1
7.5

Weather dependent regulation

When connecting an outdoor sensor, the leaving water temperature is automatically
regulated dependent on the outdoor temperature, in accordance with the set fuel line.
The maximum leaving water temperature (Tmax) is set via the temperature display. If
so desired, the fuel line can be changed by using the service code (see par.7.2). The
weather dependent regulation only functions with an on-off thermometer. When
applying an Open Therm room thermostat, the outside temperature is passed on, but
the fuel line of the CH boiler is not active.
Fuel line graph
X.
T outside in °C
Y.
T leaving water in °C
A.
Factory setting
(Tmax CH = 80°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)
B.
Example
(Tmax CH = 60°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)
Settings on service display
(in % maximum rpm)
33
31.9
100
28.8
90
25.6
80
22.4
70
19.2
60
16.0
50
12.8
40
8.0
25
Set power (kW)
5.4 kW
8.5 kW
17.8 kW
26.2 kW
42