ADEUNIS LoRaWAN AS-923 Pulse Guide Utilisateur page 74

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LoRaWAN AS-923 Pulse - Guide utilisateur / User guide version V1.0.0
327
2
328
2
329
2
FR
330
2
EN
331
2
332
1
333
1
334
1
335
1
Flow threshold (channel B)
Leak threshold (channel A)
Leak threshold (channel B)
Number of daily periods under
the leak threshold (channel A)
Number of daily periods under
the leak threshold (channel B)
Scan period for Channel A
tamper input
Tamper detection threshold
channel A
Scan period for Channel B
tamper input
Tamper detection threshold
channel B
Decimal
Default value :0 (deactivated)
Min/max : 0 to 65535
Unit: pulses per hour
Decimal
Default value: 0
Min/max : 0 to 65535
Unit : pulses per hour
Decimal
Default value: 0
Min/max : 0 to 65535
Unit : pulses per hour
Decimal
Default value: 0 (deactivated)
Min/max : 0 to 1440
Unit : none
The multiplication of this register by the period of flow measu-
rement must be less than 24 hours otherwise the product will
be perpetually in alarm.
Decimal
Default value: 0 (deactivated)
Min/max : 0 to 1440
Unit : none
The multiplication of this register by the period of flow measu-
rement must be less than 24 hours otherwise the product will
be perpetually in alarm.
Decimal
Default: 2
Min/Max: 1 to 255
Unit: x10 seconds
Decimal
Default: 3
Min/Max: 1 to 255
Unit: none
Number of positive scans of A-channel tamper before trigge-
ring the tamper alarm
Decimal
Default: 2
Min/Max: 1 to 255
Unit: x10 seconds
Decimal
Default: 3
Min/Max: 1 to 255
Unit: none
Number of positive scans of B-channel tamper before trigge-
ring the tamper alarm
Page