ADEUNIS LoRaWAN AS-923 Pulse Guide Utilisateur page 73

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LoRaWAN AS-923 Pulse - Guide utilisateur / User guide version V1.0.0
321
1
322
1
323
4
324
4
325
2
326
2
History configuration (chan-
nels A and B)
Debounce filter period (pulse
minimum width) (channels A
and B)
Current value of meter -
channel A
Current value of meter -
channel B
Flow calculation period (chan-
nels A and B)
Flow threshold (channel A)
Hexadeci-
Default value : 0x00
mal
Bits 0 to 2: History configuration
Value 0: no history
Value 1: history period set to 10min / transmit period set
to 1 hour
Value 2: history period set to 1 hour / transmit period set
to 24 hours
Hexadeci-
Default value: 0x22
mal
Bits 0 to 3 : debounce filter period - channel A
Value 0: desactived
Value 1: 1 ms
Value 2: 10 ms
Value 3: 20 ms
Value 4: 50 ms
Value 5: 100 ms
Value 6: 200 ms
Value 7: 500 ms
Value 8: 1 s
Value 9: 2 s
Value A: 5 s
Value B: 10 s
Value C à F : reserved
Bits 4 to 7 : debounce filter period - channel B
Value 0: désactivé
Value 1: 1 ms
Value 2: 10 ms
Value 3: 20 ms
Value 4: 50 ms
Value 5: 100 ms
Value 6: 200 ms
Value 7: 500 ms
Value 8: 1 s
Value 9: 2 s
Value A: 5 s
Value B: 10 s
Value C à F : reserved
Decimal
Default value: 0
Min/max : 0 to (2
32-1
Unit : number of pulses
In COMMAND mode, it is possible to write a new value in this
register (for example an initialization value, an adjustment
value ...).
Decimal
Default value: 0
Min/max : 0 to (2
32-1
Unit : number of pulses
In COMMAND mode, it is possible to write a new value in this
register (for example an initialization value, an adjustment
value ...).
Decimal
Default value: 60
Min/max : 1 to 1440
Unit :
x 1min if S306=1
x 20s if S306=2
Decimal
Default value :0 (deactivated)
Min/max : 0 to 65535
Unit: pulses per hour
)
)
FR
EN
Value
Page
73
of 99