Conto D4-Pd

5 Energy pulse output

(where provided)
PLSt
5.1
Associated energy
Selectable values : ACt (active energy) – rEA (reactive energy)
selectes energy
Page
increases/decreases the loaded value
Prog
confirms
Page + Prog
5.2
PLSU
Pulse weight
Selectable values
Active energy:
1 pulse/Wh – 1 pulse/10Wh – 1 pulse/100Wh –
1 pulse/1000Wh – 1 pulse/10kWh
Reactive energy:
1 pulse/Wh - 1 pulse/10/varh – 1 pulse/100/varh –
1 pulse/1000varh – 1 pulse/10kvarh
selectes the value
Page
increases/decreases the loaded value
Prog
confirms
Page + Prog
PLSd
5.3
Pulse duration
Selectable values: 50 – 100 – 150 – 200 – 300 – 400 – 500ms
selectes the value
Page
increases/decreases the loaded value
Prog
confirms
Page + Prog
6

6 Run hour meter

thr
6.1
3-phase active power threshold, to start count
Selectable values: 0,4...50%Pn
Pn = 3-phase active power
(referred to 400V 10A = 6900W)
moves the cursor
Page
increases/decreases the loaded value
Prog
confirms
Page + Prog
th
6.2 rS
Run hour meter count reset mode
Selectable values: YES
(count resettable through keyboard)
selectes YES or no
Page
increases/decreases the loaded value
Prog
confirms
Page + Prog
ATTENTION:
by selecting no
(count not resettable through keyboard)
reset run hour meter count through keyboard; besides, in the ensuing access to
programming, it will be available just the power threshold selection
while is inhibited the possibility to select the reset mode

7 CodE 1000

Confirm password
Confirm or modify programming access
moves the cursor
Page
increases/decreases the loaded value
Prog
confirms
Page + Prog
If you don't want to modify the default
to confirm the existing Password.
ATTENTION!
It is essential that you record and store in a safe way the modified Password in order
to access to the programming menu at a future time.
- no
(count not resettable through keyboard)
it is not possible to
,
(point 8.1)
.
(point 8.2)
Password
Password
(1000), press
Page