Determining Your Airflow Requirement - Fantech VHR150 Manuel D'installation

Ventilateur récupérateur de chaleur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4

DETERMINING yOUR AIRFLOw REqUIREMENT

1 CFM = 0.47 L/s
1 L/s = 2.13 CFM
ASHRAE method
Floor area
Ft 2
m 2
< 1500
<139
1501-3000
139.1-279
3001-4500
279.1-418
4501-6000
418.1-557
6001-7500
557.1-697
>7500
>697
* ASHRAE 62.2-2010 Table 4.1, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings.
Bathroom: If the HRV is going to provide the required local exhaust ventilation for each bathroom with each a continuous 20 CFM
(10 L/s), this ventilation rate can be considered as part of the whole-building ventilation rate.
fantech
Room Count Method
Room classification
Master bedroom
Basement
Bedrooms
Living room
Others
Kitchen
Bathroom
Laundry room
Utility room
Ventilation Air requirements
0-1
2-3
CFM
L/s
CFM
30
14
45
45
21
60
60
28
75
75
35
90
90
42
105
105
50
120
Number of rooms
if yes add 10 L/s (20 CFM)
yes or no
if no = 0
Total Ventilation Requirements (add last column )
Bedrooms
4-5
L/s
CFM
L/s
CFM
21
60
28
28
75
35
35
90
45
105
42
105
50
120
50
120
57
135
57
135
64
150
CFM (L/s)
CFM Required
x 10 L/s (20 CFM)
x 5 L/s (10 CFM)
x 5 L/s (10 CFM)
x 5 L/s (10 CFM)
x 5 L/s (10 CFM)
x 5 L/s (10 CFM)
x 5 L/s (10 CFM)
x 5 L/s (10 CFM)
6-7
>7
L/s
CFM
75
35
90
90
42
105
50
120
57
135
64
150
71
165
=
=
=
=
=
=
=
=
=
=
L/s
42
50
57
64
71
78