Models K-1100, LX2, K-2300, and LEV110CK/2G
5.5

Fill Will Not Turn ON

This is a troubleshooting flow chart for models K-1100, LX2, and LEV110CK/2G. Use it when the Fill function will
not turn on.
Disconnect blue valve
wires from control box.
green fill light
NO
Disconnect orange
sensor wires at
control box.
YES
Does sensor
light turn on?
NO
No power.
PBC board is bad.
|
Lockout sequence
has taken effect.
Call technical support
1 800 822 7933
Does
turn on?
YES
Sensor is bad.
Less power.
Verify correct input
voltage to unit.
Installation and Operation Manual
Fill Will Not Turn ON
Is power
light on?
YES
YES
Is fill
light red?
Pull sensor out of water.
Does sensor
light turn on?
NO
Wait 20 seconds.
NO
Does
green fill light
turn on?
NO
Check blue wires with AC
voltmeter. Is there 24 VAC?
Check for power at valve
connection. Is there power?
Cable connection between
valve and controller is bad.
ENGLISH
NO
Does unit have power?
YES
Transformer
is bad.
NO
YES
YES
YES
YES
NO
Valve is bad.
Page 21
NO
Turn on
power.