B
NOTE
y For AC cable connections, the cross-sectional area of lead wire between 2.5 mm
2
mm
is recommended.
y AC cable is not supplied on this product package. The system installer is responsible for
selecting proper components for the installation.
y The recommecded cable diameter for the AC cable gland is 16 mm. (including sheath)
C
12 mm
NOTE
It is recommended to use a yellow green stripe wire for the PE grounding connection.
PE
N
50 mm
Pass the AC cable through the cable
gland, rubber seal and housing as
shown in the figure.
Strip the AC cable as shown in the
figure.
1. Strip 50 mm off the AC cable.
2. Strip 12 mm off the every wires.
Installation
33
2
2
and 6