Refrigerant Piping - Mitsubishi Electric PAC-MKA50BC Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Dimensions and required servicing space of Branch Box
(inch)
(1)
B
Fig. 4-6
Fig. 4-8
(3)
G
Fig. 4-9
(inch)
Fig. 4-10
Fig. 4-12

5. Refrigerant piping

* Always follow the specifi cations written in the installation manual of the outdoor unit. Exceeding these requirements may cause reduced performance of the equipment,
and malfunctions.
6
(2)
C
A
*1
D
E
*3
Fig. 4-7
E
D
Fig. 4-11
NO
NO
YES
NO
(inch)
4.2. Space required for installation and servicing
1. The space when installing with the suspension bolts.
(1) Front View (Fig. 4-6)
Branch box
A
On the side of piping
B
(2) Side View (Fig. 4-7, Fig. 4-8)
*2
For indoor installations
C
Ceiling board
D
Maintenance hole
E
*1: Minimum 13-3/4 inch (350 mm) is required for 90° bends in refrigerant piping.
*2:
is " Min. 7-7/8 inch (200 mm)" <recommendation>.
(Premise: The slope of drain piping is securable 1/100 or more. Required
(inch)
7-7/8 inch (200 mm) or more, when not securable.)
In the case of less than 7-7/8 inch (200 mm) (for example
mm)), the exchange work of Branch box from a maintenance hole becomes dif-
fi cult (Only exchange work of a PCB, linear expansion valve coils and sensors
are possible).
*3:
is "
23 - 5/8 inch (600 mm)" <recommendation>.
In the case of "
17-3/4 inch (450 mm)", prepare a maintenance hole at a PCB
side (as it is shown in Fig. 4-8), and "Min. 11-13/16 inch (300 mm)" is needed as
distance
.
In the case of less than 11-13/16 inch (300 mm) (for example
(inch)
mm)), the exchange work of Branch box, linear expansion valve coils and
sensors from a maintenance hole becomes diffi cult (Only exchange work of a
PCB is possible).
(3) Top View (Fig. 4-9)
Refrigerant piping
G
2. The space when installing on the fl oor. (Fig. 4-10)
(inch)
3. The space when installing on a wall. (Fig. 4-11)
The installation direction is limited when installing on a wall. (Fig. 4-12)
When installing the unit on the wall, install the piping connected to the outdoor
unit facing down. Other ways are not acceptable.