THERMASGARD
Calibratable outside temperature measuring transducer THERMASGARD
sensor, continuous output, terminal box enclosure made of impact-resistant plastic, enclosure cover with quick-locking screws, with or without
optional display. For the detection of outside temperatures, temperatures in wet room areas, e.g. for installation on outside walls, in cold storage
buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas preferably at the north side of a building or in a
protected place. In case of direct sun irradiation, the sunshade and ball game protection WS 01 (accessories) or the device variant with the installed
sunshade SS 02 (available on request) must be used. These outdoor sensors are factory-calibrated. Adjustment ⁄ fine adjustment by the user is
possible (zero point offset is adjustable).

TECHNICAL DATA

Power supply:
Working resistance:
Load resistance:
Power consumption:
Sensor:
Measuring ranges:
Deviation, temperature:
Output:
Ambient temperature:
Connection type:
Process connection:
Enclosure:
Enclosure dimensions:
Cable gland:
Electrical connection:
Humidity:
Protection class:
Protection type:
Standards:
Optional:
THERMASGARD
®
ATM 2 – Outside temperature ⁄ wet room temperature measuring transducers
Type ⁄ WG01
ATM 2 - I
AT M 2 - I
AT M 2 - I _ D I S P L AY
ATM 2 - U
AT M 2 - U
AT M 2 - U _ D I S P L AY
Extra charge:
ATM 2
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant,
depending on working resistance, residual ripple stabilised ± 0.3 V
R
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant
a
b
R
> 5 kOhm for U variant
L
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
Pt1000, DIN EN 60751, class B, (Perfect Sensor Protection)
sensor inside external stainless steel sensor tube, 1.4571, V4A
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
± 0.2 K at +25 °C
0 - 10 V or 4...20 mA
measuring transducer –30...+70 °C
2- or 3-wire connection
by screws
plastic, material polyamide,
30 % glass-globe-reinforced,
with quick-locking screws,
(slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016),
enclosure cover for display is transparent!
72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
0.14 - 1.5 mm² via terminal screws
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity,
electromagnetic compatibility according to
EN 61326, according to EMC directive 2014 ⁄ 30 ⁄ EU
Two-line display with illumination,
cutout approx. 36 x 15 mm (W x H), for displaying the
ACTUAL temperature and the internal diagnostics
(measuring range exceeded, measuring range not
reached, sensor breakage, sensor short circuit)
Sensor
Output
Pt1000
4...20 mA
Pt1000
4...20 mA
Pt1000
0 - 10 V
Pt1000
0 - 10 V
Other ranges optional
with sunshade SS 02
®
ATM 2 with eight switchable measuring ranges, internal or remote
Display
Display
Rev. 2017 - V12 GB
Standard
Measuring range
exceeded
Measuring range
not reached
Sensor
breakage
Sensor
short circuit
Item No.
IP 65, I - variant
1101- 1142- 0009-900
1101-114 2-2009- 900
IP 65, U - variant
1101- 1141- 0009-900
1101-114 1-2009- 900
on request