HYGRASREG
TW
Patented quality product (pro-dynamic cross convection patent no. DE 10 2012 015 726.6)
The dew point control switch HYGRASREG
by means of its humidity and temperature sensor (no conductivity measurement) and, thanks to its patented measuring method, pro-dynamic cross
convection, yields an exact measurement result (with LED status display), with ⁄ without display. Dew point temperature is that temperature at
which air reaches the state of saturation and water vapour starts to condensate. Facilitated by the continuous measuring range from 0...100 % r.H.
of the TW-U and the adjustable switchpoint for the TW-W of 75...100 % r.H., it is possible to operate cooling ceilings, for example, so that the
switching output of the dew point control switch, the DDC, is activated and then triggers a heater or other control elements, thereby preventing the
formation of dew on pipes or cooling ceilings or on the property to be monitored.

TECHNICAL DATA

Power supply:
Power consumption:
Measuring Range:
Output:
Sensors:
Sensor protection:
Medium:
Housing:
Housing dimensions:
Cable connection:
Electrical connection:
Process connection:
Mounting:
Protection class:
Protection type:
Standards:
Optional:
FUNCTION
13 11 12
13 11 12
®
HYGRASREG
TW
HYGRASREG
®
TW - external Dew point control switches with detached sensor head (± 3 %), Deluxe
Type ⁄ WG01
Measuring Range
Humidity
TW
T W-W
75...100 % r. H.
T W-W LCD
75...100 % r. H.
T W- U
0...100 % r. H.
T W- U / W
0...100 % r. H.
T W- U / W LCD
0...100 % r. H.
TW - external
T W-W- e x t e r n
75...100 % r. H.
T W-W- e x t e r n LCD
75...100 % r. H.
Optional:
Cable connection with M12 connector according to DIN EN 61076-2-101
®
TW is installed on cooling ⁄ cold-water piping or on cooled surfaces. It reliably detects formation of dew
24 V AC (± 20 %) and 15...36 V DC
< 1.1 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
formation of dew is detected at
0...100 % r.H. on the TW-U, continuous
75...100 % r.H. on the TW-W, switching
(switchpoint adjustable by potentiometer, factory setting 75 % r.H.)
0 -10 V or potential-free changeover contact (24 V), 1 A ohmic load
digital humidity sensor with integrated temperature sensor,
small hysteresis, high long-term stability
membrane filter
clean air and non-aggressive, non-combustible gases
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced, 
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), housing cover is transparent!
72 x 64 x 43.3 mm (Tyr 1)
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable,
inner diameter 10.4 mm) or M12 connector according to DIN EN 61076-2-101
(optional on request)
0.14 - 1.5 mm², via terminal screws
endless metal strap with metal tightener, 300 mm,
for pipes up to 3 " diameter (included in the scope of delivery)
TW with strap for direct mounting on pipes
or for direct mounting on flat surfaces (e.g. walls, ceilings)
TW - external with detached sensor head
(cable length KL = 1.5 m) for mounting on pipes
III (according to EN 60 730)
IP 65 (according to EN 60 529) Housing tested, TÜV SÜD, Report No. 713139052 (Tyr 1)
CE conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
two-line display with illumination, cutout approx. 36 x15 mm (W x H),
for displaying actual humidity and the switching status of the relay
The relay output is triggered (contact 13 -11 closed)
if the pre-set switchpoint (factory setting 75 % r.H.)
is not reached and opens (contact 12 -11 closed) in the event of an error (power failure, condensation).
LED short pulses =
relay active → switchpoint not reached
ACTUAL humidity < pre-set switchpoint (no condensation)
LED long pulses =
relay inactive → switchpoint exceeded
ACTUAL humidity > pre-set switchpoint (condensation)
Dew point control switches including strap (± 3 %), Deluxe
Output
Humidity
Changeover contact
Changeover contact
0 -10 V
0 -10 V + Changeover contact
0 -10 V + Changeover contact
Changeover contact
Changeover contact
Mounting
Display
Sensor internal
for mounting directly on pipes
for mounting directly on pipes
for mounting directly on pipes
for mounting directly on pipes
for mounting directly on pipes
Sensor external
for mounting on pipes
for mounting on pipes
Rev. 2021 - V19
Item No.
IP 65
1202- 1015- 0001- 000
1202- 1015- 1201- 020
1201-1 011-1001- 020
1202- 1012- 1001- 020
1202- 1012- 1201- 020
IP 65
1202- 1015- 0021- 030
1202- 1015- 0221- 030
on request