Technical Data - Balluff BES M30EH2 Notice D'utilisation

Capteur inductif
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Instruction manual BES M30EH2-GNX15F-BT02-X05

Technical data

Certificate number
HazLoc marking
Temperature range
EPL Ga and Class I, Division 1:
T6
T5
T4
T3
EPL Gb and Class I, Division 1:
T6
T5
T4
T3
EPL Da and Class II, Division 1:
EPL Db and Class III, Division 1:
Maximum value Ui
Maximum value Ii
Maximum value Pi
Effective internal capacity Ci
Effective internal inductivity Li
Electrostatic chargeable plastic housing
With reference to group II (gas):
With reference to group III (dust):
Housing material
Rated values accord. to
UL/CSA C22.2 No.60947-5-2-14
Output function accord.
to IEC 60947-5-6
Distance / current characteristic
Switching distance Sn
Operating point
Hysteresis
Test voltage
Degree of protection [IEC 60529 Edition 2.2]
Electrical connection
Accessories
BA-S36095-GB-2020-22
CSA 20CA80041978X
Class I, Division 1, Groups A, B, C, D T6...T3
Class II, Division 1, Groups E, F, G, T145°C
Class III, Division 1
Ex ia IIC T6...T3 Ga
Ex ia IIIC T145°C Da
Class I, Zone 0, AEx ia IIC T6...T3 Ga
Zone 20, AEx ia IIIC T145°C Da
–20 °C ≤ Ta ≤ +60 °C
–20 °C ≤ Ta ≤ +60 °C
–20 °C ≤ Ta ≤ +60 °C
–20 °C ≤ Ta ≤ +60 °C
–25 °C ≤ Ta ≤ +75 °C
–25 °C ≤ Ta ≤ +90 °C
–25 °C ≤ Ta ≤ +125 °C
–25 °C ≤ Ta ≤ +140 °C
–25 °C ≤ Ta ≤ +140 °C
–25 °C ≤ Ta ≤ +140 °C
9.6 V DC
12.1 mA
29 mW
66.2 nF
1.2 mH
573 mm²
1421 mm²
AISI 316 Ti / PEEK
max. 8.3 V, 3 mA
closing
continuous
15 mm non flush
0.8 Sn
<0.1 Sn
500 V / 50 Hz / 60 s
IP 68 (3 bar), IP 69
2 m FEP-cable, blue, 2x0.34 mm²
2x nut M30x1.5, AISI 316
Page 2
Dok.-Nr. 947410-EN/FR-E20
Subject to modification

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Gnx15fBt02X05

Table des Matières