Air Damper Adjustment; Electrode Setting; Burner Start-Up Cycle - Chappee TIGRA 2 CF 910 Manuel D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.6

Air damper adjustment

The air damper is set in factory.
This regulation is purely indicative. Each installation however,
has its own unpredictable working conditions: actual nozzle ou-
tput; positive or negative pressure in the combustion-chamber,
the need of excess air, etc.
All these conditions may require a different air damper setting
(see Tab. A).
The purpose of this damper is to perform a fine-tuning of the in-
let air. Tuning of this device is possible acting of the
screw 1)(Fig. 19).
3.7

Electrode setting

Check the position of the factory set electrodes complying with
the Fig. 20. Before removing or assembling the nozzle, loosen
the screw 1)(Fig. 20) and move the electrodes ahead.
Measures must be respected.
WARNING
3.8

Burner start-up cycle

Normal
Limit thermostat
Fan motor
Ignition transformer
Oil valve
Flame
Lock-out signal
(*) Lock out is indicated by a lamp on the control box 4)(Fig. 1).
20018260
Burner operation
A
D9872
~12s
Model
TIGRA 2 CF 910
TIGRA 2 CF 1210 1A ML
Lock-out due to failure to light *
~12s
12
GB
D9861
1
A
2.5 ± 0.3
3 ± 0.3
+ 0 . 5
1 . 5
0
D
~5s
Fig. 19
Fig. 20
D5529

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

C20017827Tigra 2 cf 1210 1a mlC20018230989t990t

Table des Matières