For battery cables up to 3 metres, the cross-section of the battery cables should be at least equal to or greater than
the values provided in the table below:
0V common (Output +24V and Input +24V)
0V common (Output +12V or Input +12V)
The installer should choose the type of cable (H07-VK, MX, etc.) according to the type of application and the applicable
standards. The connection is made by bolting ring terminals to the 3 electrical power studs.
+12V DC input or
+24V DC input
0V common
+24V DC output or
+12V DC output

3.2.2 Precautions regarding electromagnetic disturbance generated by the appliance

We recommend a minimum distance of 2m between the charger and any potentially sensitive equipment.
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and the
receiving ends.
Keep cable length and shielding connections to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables should be
placed against the hull or walls).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any deviation to power another appliance is prohibited.
Cable
Input +12V
Input +24V
Output +12V
Output +24V
Battery cable cross-section
10mm²
25mm²
25mm²
10mm²
25mm²
10mm²