9. Electrical wiring

Precautions on electrical wiring
Warning:
Electrical work should be done by qualified electrical engineers in accord-
ance with "Engineering Standards For Electrical Installation" and supplied
installation manuals. Special circuits should also be used. If the power cir-
cuit lacks capacity or has an installation failure, it may cause a risk of elec-
tric shock or fire.
1. Be sure to install an earth leakage breaker to the power.
2. Install the unit to prevent that any of the control circuit cables (remote control-
ler, transmission cables) is brought in direct contact with the power cable out-
side the unit.
3. Ensure that there is no slack on all wire connections.
4. Some cables (power, remote controller, transmission cables) above the ceiling
may be bitten by mouses. Use as many metal pipes as possible to insert the
cables into them for protection.
5. Never connect the power cable to leads for the transmission cables. Other-
wise the cables would be broken.
<Table 1>
System configuration
Transmission cable length
Facility example
Residence or independent store
(for noise judgment)
without noise
VCTF, VCTFK, CVV, CVS, VVR,
Types of transmission
VVF, VCT or shielding wire
cables
CVVS or CPEVS
Length
2. Remote controller cables
Types of cables
Sheathed 2-core cable (unshielded) CVV
Cable diameter
0.3 to 1.25 mm
Less than 200 m [656 ft]
Length

9.1. Power supply wiring

Power supply cords of appliances shall not be lighter than design 245 IEC 57
or 227 IEC 57.
A switch with at least 3 mm [1/8 in] contact separation in each pole shall be
provided by the Air conditioner installation.
Power cable size: more than 1.5 mm
[Fig. 9.1.1] (P.4)
A Switch 16 A
C Indoor unit
D Total operating current be less than 16 A
E Pull box
[Selecting non-fuse breaker (NF) or earth leakage breaker (NV)]
To select NF or NV instead of a combination of Class B fuse with switch, use the
following:
In the case of Class B fuse rated 15 A or 20 A,
NF model name (MITSUBISHI): NF30-CS (15 A) (20 A)
NV model name (MITSUBISHI): NV30-CA (15 A) (20 A)
Use an earth leakage breaker with a sensitivity of less than 30 mA 0.1 s.
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using
fuse, wire or copper wire with too large capacity may cause a risk of mal-
function or fire.
For a single-refrigerant system
Less than 120 m [394 ft]
Building, clinic, hospital or communications
station without noise supposedly generated
from inverter equipment, private power gen-
erator, high-frequency medical equipment,
radio-used communications equipment and
so on
Less than 120 m [394 ft]
MA remote controller
2
[AGW22 to 16]
2
[AWG16]
B Overcurrent protection 16 A
6. Be sure to connect control cables to the indoor unit, remote controller, and the
outdoor unit.
7. Put the unit to the ground on the outdoor unit side.
8. Select control cables from the conditions given in page 11 .
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not con-
nect the earth cable to any gas pipe, water pipe, lightening rod, or telephone
earth cable. Incomplete grounding may cause a risk of electric shock.
Types of control cables
1. Wiring transmission cables
Types of transmission cables
Design wiring in accordance with the following table <Table 1>.
Cable diameter
2
More than 1.25 mm
[AWG16]
More than 120 m [394 ft]
Shielding wire CVVS or CPEVS
M-NET remote controller
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
2
[AGW22 to 16]
Add any portion in excess of 10 m [32 ft] to within the longest allowable
transmission cable length 200 m [656 ft] (Shielding portion is more than
1.25 mm
2
[AWG16])
9.2. Connecting remote controller, indoor
and outdoor transmission cables
Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
Install a remote controller following the manual supplied with the remote con-
troller.
Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller.
(Non-polarized 2-wire)
Connect the remote controller's transmission cable within 10 m [32 ft] using a
2
0.75mm
[AWG18] core cable. If the distance is more than 10 m [32 ft], use a
1.25 mm
2
[AWG16] junction cable.
[Fig. 9.2.1] (P.4) MA Remote controller
[Fig. 9.2.2] (P.4) M-NET Remote controller
A Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable
C Remote controller
DC 9 to 13 V between 1 and 2 (MA remote controller)
DC 24 to 30 V between M1 and M2 (M-NET remote controller)
[Fig. 9.2.3] (P.5) MA Remote controller
[Fig. 9.2.4] (P.5) M-NET Remote controller
A Non-polarized
C Remote Controller
The MA remote controller and the M-NET remote controller cannot be used at
the same time or interchangeably.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension
may break, or overheat and burn.
For a multi-refrigerant system
Regardless of length
All facilities
Less than 200 m [656 ft]
B TB15
D TB5
11