Explication of the thresholds and their hysteresis:
FR
EN
The settings associated with this mode of operation are:
• Sampling period (register 321).
• The activation of the probes (register 324).
• Alarm configuration of the probe 1 (register 330) and probe 2 (register 340).
• High threshold of the probe 1 (register 331) and probe 2 (register 341).
• Hysteresis for the high threshold of the probe 1 (register 332) and probe 2 (register 342).
• Low threshold of the probe 1 (register 333) and probe 2 (register 343).
• Hysteresis for the low threshold of the probe 1 (register 334) and probe 2 (register 344).
Example :
Register Encoding
S301
Decimal
S321
Decimal
S324
Decimal
S330
Decimal
S331
Decimal
S332
Decimal
S333
Decimal
S334
Decimal
S340
Decimal
S341
Decimal
S342
Decimal
S343
Decimal
S344
Decimal
In this example:
• The product measure the temperature on the 2 probes every hour
• On probe 1, there is a high alert at 70°C with a come back to normal at 65°C and a low alert at 10°C with a come back to normal at 12°C
• On probe 2, there is only a high alert at 23.5°C with a come back to normal at 20°C
High alarm enabling
Value
Result
0
Alarm mode
1800
A sample of the temperature every hour
3
The 2 probes are activated
3
An alarm is activated on high and low threshold on the probe 1
700
High threshold is 70°C
50
Hysteresis of the high threshold is 5°C, so the come back to normal is at 65°C
100
Low threshold is 10°C
20
Hysteresis of the low threshold is 2°C, so the come back to normal is at 12°C
2
An alarm is activated on high threshold only on probe 2
235
High threshold is 23.5°C
35
Hysteresis of the high threshold is 3.5°C, so the come back to normal is at 20°C
0
No low threshold determined
0
No low threshold determined
high threshold
High threshold -
Sensor value
Low threshold +
Low threshold
Low alarm enabling
High alarm disabling
high threshold hysteresis
low threshold hysteresis
Low alarm disabling