Function and features

The slave converts analogue input signals and transfers them to the
AS-i master via the AS-Interface. The AS-i module operates as a slave
with bidirectional data transfer in the AS-i network.
The data transfer to the host is asynchronous according to the AS-i
profile S-7.3 and the AS-i specification V2.1.
• Current measurement 4...20 mA (AC2616)
or voltage measurement 0...10 V (AC2617)
• AS-i profile S-7.3.D
• The sensors are connected via cage clamps
• Maximum number of modules per AS-i system: 31
• R
voltage measurement > 100 kΩ ; R
i
• Time for converting the measured values in the slave
- for one channel: 20 ms
- for two channels: 120 ms
• Sensor supply from AS-i (max. 90 mA) or external 24 V PELV voltage
source (black flat cable)
• 16-bit resolution
• 50 Hz or 60 Hz filter in the A/D converter, parameter setting via the
parameter bit P0
LEDs 1... 5
links
cage clamps
current measurement < 50 Ω
i
1 I+ sensor supply 2 +24 V
2 C2 analogue input current (AC2616)
V2 analogue input voltage (AC2617)
3 I - sensor supply 2 0 V
4 COM2 analogue input 2 0 V
5 Shield
6 Shield
7 I+ sensor supply 1 +24 V
8 C1 analogue input current (AC2616)
V1 analogue input voltage (AC2617)
9 I - sensor supply 1 0 V
10 COM1 analogue input 1 0 V
11 FE functional earth
12 FE functional earth
LED1 (yellow) status analogue input 1
LED2 ( yellow) status analogue input 2
LED3 (green) A/D power
LED4 (green) AS-i
LED5 (red) FAULT
Links:
Sensor supply from AS-i/24 V external