1. Preparation of the gate
Make sure that the gate is properly installed and slides smoothly before installing the gate operator.
The gate must be level and move freely.
Electric cable
In order to protect the cable, use PVC conduits for low voltage power cables and control
wires. The conduit must be preset into the concrete when it is poured. The wires inside
the cables should be located and protected in such way that no damage can result from
contact with any rough or sharp parts.
WARNING
Before installing the gate operator, check that the driven part is in good mechanical
condition, correctly balanced and can be opened and closed properly.
The control device cannot be installed over 2.5 m above the floor. The control
device and drive device should be installed toghther on the ground.
The product cannot control the wicket door. A drive device cannot control 2 doors
at the same time.
When installing the product, check that the maximum distance from the wall is
no more than 200 mm. The maximum distance from the ground cannot exceed
50 mm.
Please follow the installation instructions when installing the drive device.
The actuating member of a biased-off switch should be located within direct sight
of the driven part but away from moving parts. If it is not operated with the key,
it should be installed at a minimum height of 1.5 m above the ground and not
accessible to the public.
After installation, ensure that the mechanism is properly adjusted and that the
protection system and any manual release function correctly.