Create an air intake (minimum air passage cross-section 200 cm
if one does not exist and place it under the lower part
of the fireplace. If the fresh air intake opens directly
to the outside, it must be placed facing the dominant winds.
If there is a protection grid, ensure that passage is compatible
with the fireplace requirements. Check that the air intakes
are not blocked on a regular basis.
Danger: no fresh air intake, or one which is not adapted
to requirements may lead to combustion gases being
released into the room, causing the occupants to experience
drowsiness, nausea or faintness.
To the fireplace
The primary air inlet flue pipe (connectable) is located
on the front and under the appliance. It must not be blocked.
See figure 1 page 11 and appliance technical data sheet sent
with this manual.
If the fireplace is placed on the floor without its adjustable legs,
the convection air intake openings at the base of the stove
must be unblocked, see figure 1 page 11 and the product
technical sheet attached to this manual.
2.4 Required distances
and measurements
Openings to be made in the surround
See figure 1 page 11 and "Convection air intake and outlet"
in the product technical sheet attached to this manual.
Distance between the stove and non-inflammable backing wall
50 mm minimum in addition to the thickness of the insulation,
see drawings figures 1 and 2 page 11.
Recommended insulation
50 mm of rock wool, 90 kg/m
on one side. See figures 1 and 2 page 11.
Distance from furniture
1,3 meter minimum.
Connection flue chimney diameter
See "Connecting a flue" in the product technical sheet
attached to this manual. It is essential to maintain the smoke
outlet cross-section when connecting the flue.

3.0 Installation

Before beginning installation, ensure that the parts
of the fireplace are operating correctly (see the product
technical sheet attached to this manual):
- guillotine, side hinged or drawer door operation:
first remove the screws blocking the weigths,
identified by a fluorescent label;
- damper control operation;
- primary air vent operation.
Adjust fireplace height using the adjustable legs
(optional acessories). Mount according to model.
8
foliated with aluminium sheet
3

Adjustable legs:

)
2
RAW-SCREW TChC 8 x 30
ZINC-PLATED WAShER 8 x 18
RAW-SCREW TChC 8 x 30
RAW-SCREW Th 10 x 70
Mounting:

3.1 Protecting the backing walls

All material of a combustible nature or which may be damaged
by heat must be removed from the surrounding walls
(floors, walls and ceilings) where the fireplace is to be placed,
see figure 1 page 11.
The required insulation must be installed using class A1 or
at least M0 insulating materials, and a 50 mm minimum layer
of ventilated air between the fireplace and the insulation.
In all cases, the installation environment must be in compliance
with current legislation and regulations in the country
of installation.

3.2 The floor

The floor must be able to bear the weight of the assembled
fireplace and surround. See the product technical sheet.
Extra support may be required.

3.3 The surround

The fireplace surround must be made of non-combustible
materials (please refer to current standards).
The surround interior must be fully insulated. It is essential
to have a 50 mm minimum layer of ventilated air between
the insulation and the fireplace. See figures 1 and 2 page 11.
The surround must be self supporting and must not be
attached to the appliance. At least 3 mm clearance must be
left between the surround and the fireplace to allow
the appliance to dilate.