2.2.2 PWM SOLAR PROFILE
PWM input – solar profile
>95% - 100%
>15%- ≤95%
>12% - ≤15%
>7% - ≤12%
≤7% or no signal
2.3
PWM OUTPUT
PWM output signals flow and error information from the pump according to the bottom table.
PWM‐out
0 %
PWM output interface in short circuit
2.5 %
Pump in standby and ready
5 %
Normal operation, no flow
5..75 %
Normal operation, flow indication
75 %
Normal operation, maximum nominal flow
80 %
Error is present, performance might be reduced
85 %
Error is present, pump is still functional, but might be stopped
90 %
Error is present, pump is stopped
95 %
Error is present, pump is stopped, permanent failure, will not restart
100%
PWM output interface is open circuit or pump is not powered
Pump response
Maximum curve
Variable curve
Minimum curve
Hysteresis area
Standby
Status
10