Specifications
Standards and Approvals
EMC*
UL listed
P44210D3-000x
* Slight deviations are possible while there is interference (typ. < 2 K)
** CAUTION! – This is a Class A device for industrial use.
When used in residential areas, the device can cause radio interference.
Further Data
Ambient temperature
Operation, storage and
transport
Relative humidity
Operation, storage and
transport
Air pressure
Operating conditions
MTBF***
Design
Protection class
Mounting
Weight
*** acc. to EN 61709 (SN29500), stationary operation in well-kept rooms,
average ambient temperature 40 °C, no ventilation, continuous operation
36
Product standard EN 61326-1,
EN 61326-2-3: 2013
Emitted interference: Class A**
Immunity to interference: Industry
High voltage industrial control
equipment accessory, E356768
–40 ... +85 °C
5 ... 95 %
(no condensation during operation)
70 ... 106 kPa, altitude up to 2000 m
Stationary operation
Approx. 160 years
Modular housing with screw terminals
Housing width D1: 22.5 mm
Housing width D3: 67.5 mm
See dimension drawings for further
dimensions
Housing: IP 40, terminals: IP 20
For 35-mm DIN rail acc. to EN 60715
D1: approx. 250 g
D3: approx. 500 g