Technical data
Fuel
Maximum nominal thermal load
Neutralisation medium
Filling quantity of neutralisation medium
Weight (completely filled)
Quantity of water to be filled
Dimensions L x W x H
Condensate inlet connection
Condensate outlet connection
Maximum medium temperature
Minimum ambient temperature
4
Assembly of the neutralisation box
The neutralisation box can be combined if necessary with different condensate pumps from the
WOLF product range.
Depending upon the type of condensate drain, the outlet is to be mounted on the neutralisation
box as follows.
● Condensate pump, art. no. 20 71 267
This condensate pump is designed for use
inside the neutralisation box. No further parts
need to be installed for the condensate drain.
Achtung
The lower hole in the side panel of the neu-
tralisation box serves as an overflow protector
for the condensate pump and it is essential
that this remains open!
10
Neutralisation box up to 40 kW
Fuel oil DIN 51603 - 1
Fuel oil DIN 51603 - 6
38.8 kW
Activated charcoal + hydrolith
COB-15 / 20 / 29
5 kg
COB-15 / 20 / 29
14.8 kg
COB-15 / 20 / 29
7 l
509 x 308 x 240 mm
Ø 26 mm
R ½-inch
65°C (short-term 80°C)
frost-protected
● Condensate pump, art. no. 20 70 665
● Without condensate pump
Seal the lower hole in the side panel of the
neutralisation box with the help of the parts
contained in the scope of supply: screw plug,
1 seal and nut. Mount the 90° pipe elbow to
the upper hole in the side panel of the neu-
tralisation box using the double nipple, 2 seals
and nut.
EL standard
Bio-oil B5
COB-40
9 kg
COB-40
17.2 kg
COB-40
5 l
3062714_0210