Daikin EKHBH054BA Manuel D'installation page 28

Unité intérieure pour système de pompe à chaleur air-eau
Masquer les pouces Voir aussi pour EKHBH054BA:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

T
t
Lo_Ti
Hi_Ti
Lo_A
Hi_A
T
Target water temperature
t
T
Ambient (outdoor) temperature
A
= Shift value
[2] Disinfection function
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function field settings must be configured
by the installer according to local laws and regulations.
[2-00] Operation interval: day(s) of the week at which the
domestic hot water should be heated.
[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).
[2-02] Start time: time of the day at which the domestic hot
water should be heated.
[2-03] Set point: high water temperature to be reached.
[2-04] Interval: time period defining how long the set point
temperature should be maintained.
T
DHW
[2-03]
T
H
T
U
00.00
01.00
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user interface)
U
T
High set point temperature [2-03]
H
t
Time
WARNING
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to local laws and regulations.
Installation manual
26
+09°F (+05°C)
00
Shift value
–09°F(–05°C)
T
A
[2-04]
22.00
23.00
24.00
t
[2-02]
[3] Auto restart
When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.
NOTE
It is therefore recommended to leave the auto restart
function enabled.
Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the pr button to enable the schedule timer again.
[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).
NOTE
If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.
[4] Backup/booster heater operation and space heating off
temperature
Backup heater operation
The operation of the backup heater can altogether be enabled or
disabled, or it can be disabled depending on operation of the booster
heater.
[4-00] Status: defines whether backup heater operation is
enabled (1) or disabled (0).
[4-01] Priority: defines whether backup heater and booster
heater can operate simultaneously (0), or if the booster
heater operation has priority over the backup heater
operation (1), or if the backup heater operation has priority
over the booster heater operation (2).
NOTE
When the priority field setting is set to
ON (1), space heating performance of the
system might be decreased at low outdoor
temperatures, since in case of domestic
water heating demand the backup heater will
not be available for space heating (space
heating will still be provided by the heat
pump).
When the priority field setting is set to
ON (2), domestic water heating performance
of the system might be decreased at low
outdoor temperatures, since in case of space
heating demand the booster heater will not
be available for domestic water heating.
However domestic water heating by heat
pump will still be available.
When the priority field setting is set to OFF
(0),
make
consumption does not exceed supply limits.
Space heating off temperature
[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.
Indoor unit for air to water heat pump system
sure
that
electrical
power
EKHBH/X054BA