1.8 Run hour meter count start
Select the quantity which starts the run hour meter count: voltage or power
Voltage:
phase voltage > 10V
Power:
3-phase active rated power
Programmable value: 0...50%Pn
Pn
= 3-phase active rated power = 3-phase rated voltage Un x rated current In x√3
Un: 400V
In: 1A or 5A
= 400V x5A x √3= 3464W or 400V x1A x√3= 692,8W
Pn
1.9 RS485 communication
(where provided)
According to the models, this meter can be without communication or equipped with
RS485 ModBus RTU/TCP
Address number: 1...255
Parity bit: none – even – odd
Waiting time before answer: 3...100ms
Transmission speed: 4800 – 9600 – 19200 – 38400 bit/s
ModBus message word format
1
Just for 32-bit quantities
1.10 Pulse output
(max. 27V 50ma)
Quantity that can be coupled: active or reactive energy
Pulse weight: 1pulse/10Wh(varh) – 100Wh(varh) – 1kWh(kvarh) - 10kWh(kvarh) -
100kWh(kvarh) – 1MWh(Mvarh) - 10MWh(Mvarh)
Width of the pulse: 50 – 100 – 200 – 300 – 400 – 500ms
1.11 Harmonic Analysis
Display mode: up to the 9
th
harmonic or up to the 25
Password = 2001
Level 2
2.1 External VT or CT ratio
Vt =
External primary/secondary VT ratio
Ct =
External primary/secondary CT ratio
External CT ratio (Ct): 1...9999
External VT ratio (Vt): 1,00...10,00
For voltage direct connection (without external VT) load Vt=1,00
By modifying the
CT
and/or
VT
Password = 3002
Level 3
3.0 Communication protocols
02/18 E08 10782668 WEB E cod.MF964..
1
: Big Endian – Little Endian – Swap
th
harmonic.
(ex. TV 600/100V Vt = 6)
(ex. TA 800/5A Ct = 160)
(max. primary current 50000/5A – 10000/1A)
(max. primary voltage TV 1200V)
ratios, the KWH meters are automatically reset
(See point 3 page 21)
Phase sequence diagnostic
In the software of the device we have added a specific functionality to detect and correct
many problems concerning voltage and / or current connection.
This function can be activated through password and allows to display and modify the
connection sequence provided that the following conditions are respected:
1) The neutral wire (in a 4-wire network) is connected to the right terminal
ber 1)
2) No crossings between cables connected to CT's
nals 1 and 3 - are connected some way both to CT1 and CT2)
3) The power factor is between 1 and 0,5 - Inductive load - for each phase.
See www.imeitaly.com "TECHNICAL SUPPORT"
Optional modules
(See page 20)
By connecting some optional modules, it is possible to have further communication outputs
Nemo 96HDLe
Module
IF96001
IF96002
IF96007A
MF96411 - MF96412
IF96009
IF96012
IF96013
IF96014
IF96015
IF96001
IF96002
IF96007A
MF96421 - MF96422
IF96009
IF96012
IF96013
IF96014
IF96015
Nemo 96 HDLe
(normally num-
(e.g. avoid that on phase 1 of the meter-termi-
.
.
Output 1
Output 2
Pulse
Pulse
RS485
Pulse
RS232
Pulse
PROFIBUS
Pulse
LonWorks
Pulse
MEMORY + RS485
Pulse
M-Bus
Pulse
BACNET
Pulse
ETHERNET
Pulse
RS485
Pulse
RS485
Pulse
RS485
Pulse
RS485
Pulse
RS485
Pulse
RS485
MEMORY + RS485
Pulse
RS485
Pulse
RS485
Pulse
RS485
Output 3
RS485
RS232
PROFIBUS
LonWorks
M-Bus
BACNET
ETHERNET