RMST temperature probes
Active sensors for distances up to 200 meters
Probe configuration
Open the probe cover (attached to the sequencer panel) and set it for
the signal 4÷20mA
J8
T
J6
T
J5
J4
Section I :: User
Rhoss RMST sequencer input/output definition
Digital inputs
Function
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
ID9
ID10
ID11
ID12
ID13
ID14
Analog inputs
Function
B1
B2
B3
B4
B5
B6
B7
B8
Digital outputs
Function
NO1
Primary pump 1
NO2
NO3
NO4
Primary pump 2
NO5
NO6
NO7
Rejection device pump 1 (water/water vers.)
NO8
Rejection device pump 2 (water/water vers.)
NO9
System general alarm (from sequencer digital inputs)
NO10
Chiller general alarm + serial network alarm
NO11
Integrative/replacement boiler request
NO12
Recovery pump 1 *
NO13
Recovery pump 2 *
(*) only for EXP units
35
Centralised remote On/Off
Centralised Summer/Winter
Requested recovery*
Double Set-point (primary)
Double Set-point (recovery) *
System general alarm
Primary flow switch
Rejection device flow switch (water/water vers.)
Primary pump alarm 1
Primary pump alarm 2
Rejection device pump alarm 1 (water/water vers.)
Rejection device pump alarm 2 (water/water vers.)
Recovery pump alarm 1 *
Recovery pump alarm 2 *
Primary shifting Set-point (signal 4-20mA)
System return water temperature probe
System flow water temperature probe
Outdoor air temperature probe
Recovery flow switch *
Recovery shifting Set-point (signal 4-20mA) *
Recovery return water temperature probe *
Recovery flow water temperature probe *