27
Floating charging voltage
29
Low DC cut-off voltage
Solar power balance:
When enabled, solar input
power will be automatically
31
adjusted according to
connected load power.
Bulk charging time(C.V
32
stage)
Bulk charging time(C.V
32
stage)
33
Battery equalization
34
Battery equalization voltage
35
Battery equalized time
21
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 08 17 AA 59 201 05
default setting: 54.0V
If self-defined is selected in program 5, this program can be
set up. Setting range is from 48.0V to 58.4V. Increment of
each click is 0.1V.
default setting: 42.0V
If self-defined is selected in program 5, this program can be
set up. Setting range is from 40.0V to 48.0V. Increment of
each click is 0.1V. Low DC cut-off voltage will be fixed to
setting value no matter what percentage of load is connected.
Solar power balance
enable (Default):
Solar power balance
disable:
Automatically (Default):
5 min
900 min
If "USE" is selected in program 05, this program can be set
up.
Battery equalization
If "Flooded" or "User-Defined" is selected in program 05, this
program can be set up.
Default setting: 58.4V. Setting range is from 48V ~ 58.4V.
Increment of each click is 0.1V.
60min (default)
If selected, solar input power will
be automatically adjusted
according to the following formula:
Max. input solar power = Max.
battery charging power +
Connected load power.
If selected, the solar input power
will be the same to max. battery
charging power no matter how
much loads are connected. The
max. battery charging power will
be based on the setting current in
program 02.
(Max. solar power = Max. battery
charging power)
If selected, inverter will judge this
charging time automatically.
The setting range is from 5 min to
900 min. Increment of each click is
5 min.
The setting range is from 5 min to
900 min. Increment of each click is
5 min.
Battery equalization disable
(default)
Setting range is from 5min to
900min. Increment of each
click is 5min.