Technical Information

Nominal Height (mm)
Dimensions
Depth (mm)
Length (mm)
Sound Pressure (dBA)
(at 2.5m)
*
Sound Levels
Sound Power (dBA)
(at 2.5m)
Motor
Power (W)
2 Pipe Water Content (l)
4 Pipe Water Content (l)
Weight and
Water Content
2 Pipe Unpacked Weight (kg)
4 Pipe Unpacked Weight (kg)
Pressure Drop (kPa)
(2 Pipe Heating/Cooling
& 4 Pipe Cooling)
Flow Rates/
Pressure Losses
Pressure Drop (kPa)
(4 Pipe Heating)
* Sound levels tested in accordance with ISO 3741. Sound performance show at fan speeds via controls unit - may differ with external controller.
2 pipe water content = 2 pipe heating/cooling or 4 pipe cooling and 4 pipe water content = 4 pipe heating.

Electrical Data

All Vido models rated by an electrical supply of 100-240V
50/60Hz fused at 3A.
Fan
Speed
iV60x080
iV60x100
-
600
600
-
153
153
-
800
1000
Low
20.3
19.7
Medium
34.5
32.1
High
43.8
41.4
Low
33.2
32.6
Medium
47.5
45.0
High
56.7
54.3
Low
3.5
3.6
Medium
6.5
8.5
High
13
18.5
-
0.66
0.92
-
0.33
0.46
-
22.8
27.7
-
24.8
30.1
Flow
(l/h)
iV60x080
iV60x100
100
0.7
1
150
1.4
2.1
220
2.9
4.1
330
6.1
8.5
500
13
17.8
750
27.5
36.5
100
1.4
2
150
2.8
4.2
220
5.8
8.2
330
12.2
17
500
26
35.6
Model
iV60x120
iV60x140
iV60x160
600
600
600
153
153
153
1200
1400
1600
21.9
21.4
20.3
33.3
35.2
34.6
41.6
43.9
43.8
34.8
34.3
33.2
46.2
48.1
47.5
54.5
56.8
56.7
3.8
4.5
4.6
9.2
12
13.5
23
30
35
1.19
1.45
1.72
0.6
0.73
0.86
32.5
37.5
42.6
35.3
40.7
46.2
Model
iV60x120
iV60x140
iV60x160
1.4
1.6
1.9
2.9
3.2
3.7
5.5
6.1
7.1
11.1
12.2
14.2
22.9
24.9
28.7
46.2
49.8
57.1
2.8
3.2
3.8
5.8
6.4
7.4
11
12.2
14.2
22.2
24.4
28.4
45.8
49.8
57.4