7.2. Assembly instructions
1. Thoroughly flush pipework
2. Install pressure reducing valve
• Note flow direction
• Install without tension or bending stresses
3. Seal pressure gauge
8. Start-up

8.1. Setting outlet pressure

Set outlet pressure 1 bar minimum under inlet 
pressure.
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen hexagon nut on spring bonnet
5. Slacken tension in compression spring
6. Slowly open shutoff valve on inlet
7. Rotate adjustment screw, until the pressure gauge shows
the desired value
8. Retighten hexagon nut
9. Slowly open shutoff valve on outlet
9. Maintenance
We recommend a planned maintenance contract with
an installation company
In accordance with DIN EN806-5, the following measures
must be taken:
9.1. Inspection

9.1.1. Pressure reducing valve

Interval: once a year
1. Close shutoff valve on outlet
2. Check outlet pressure using a pressure meter when there
is zero through-flow
• If the pressure is increasing slowly, the valve may be
dirty or defective. In this instance, carry out servicing
and cleaning
3. Slowly open shutoff valve on outlet
9.2. Maintenance
Frequency: every 1-3 years (depending on local
operating conditions)
To be carried out by an installation company
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen hexagon nut on spring bonnet
Caution !
There is a spring in the spring bonnet. It may cause
injuries if the spring is derailing.
• Make sure tension in compression spring is slak-
kened!
5. Slacken tension in compression spring
Honeywell GmbH
GB
• Turn control adjustment screw to the left (-) until it does
not move any more
6. Unscrew spring bonnet
7. Check the cartridge insert for fault-free condition and
replace insert or sealing parts if necessary.
8. Reassemble in reverse order
10. Disposal
• Housing made of ductile cast iron 
(EN-GJS-400-15 EN1563), coated with PA (polyamide)
• Spring bonnet made of ductile cast iron 
(EN-GJS-400-15 EN1563), coated with PA (polyamide)
• Cartridge insert made from stainless steel with stainless
steel valve spindle
• Spring steel adjustment spring
• Diaphragm and seals made of EPDM
• Groove ring and sealing disc made of high-quality PU
• Stainless steel screws and nuts
Observe the local requirements regarding correct waste
recycling/disposal!