Installation Instructions / Operation; Principle Of Deionization Of Water By Use Of Ion-Exchange Resins; Connection Principle For Filling Heating Systems - ELECTOR PUROFILL Manuel De L'utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PUROFILL
Chapter 3 – Installation instructions / operation

3.1 Principle of deionization of water by use of ion-exchange resins

The PUROFILL filter cartridge contains ion-
exchange mixed bed resin beads for the total
Tap water
DI-water
deionization of water. These ion-exchange resin
beads absorb the salts (ions) dissolved in the
water while the water flows through the so-called
resin bed.
When flowing through the cartridge, deionized
water (demineralized water, DI-water) is produced,
whereby an electrical conductivity of <0.1 μS/cm
can be achieved.
As the saturation of the ion-exchange resin
increases, salts break through the resin bed from
a certain point, which increases the electrical
conductivity. Beginning from an electrical
conductivity of 10 μS/cm, the ion-exchange resin
is considered to be exhausted and should be
replaced for further operation of the filter cartridge.
A defined contact time of the water with the ion-exchange resin beads is necessary for an ideal
deionization result. For this reason, the flow rate specified in the technical data should always be
observed.

3.2 Connection principle for filling heating systems

FI
www.elector-water-treatment.com
Page 24