 R450 Values
Designation
General safety LP switch
Compressor safety HP switch 1
Regulated LP switch 1
Compressor safety HP switch 2
Regulated LP switch 2
LP frame switch
HP frame switch
Adjust the thermal magnetic circuit breakers GV(x) according to the values shown in the wiring diagram on page 6
or 7
Disconnect all circuit-breakers in the electrical cabinet
Set the KT7 delay time to 30 minutes, ie the top slider for 6 to 60 minutes and the bottom slider on 5
Set the KT1 delay time to 6 minutes, ie the top slider for 1 to 10 minutes and the bottom slider 6
Set the KT2 delay time to 7mn, ie the top slider for 1 to 10 min and the bottom slider 7
Equip yourself with your electrical PPE
Close the main disconnect switch
Check the voltage before and after of the disconnect switch and before of all circuit-breakers
Using the phase controller check the order of these, the direction must be clockwise otherwise the compressors
will be irreversibly damaged.
Close the control circuit breaker Q77 (both condenser fans will run after 30 minutes if the low pressure (LP) is
higher than the BPE switch-on value. To avoid this, lower the LP pressure below the BPE and the HP pressure below
HPE)
Close transformer circuit breaker QF2
Adjust the fluid used in the P RACK controller by following the instructions below
DUO CU
GB
Pressure switch setting sheet
Abbreviation
Temperature °C
BPG
-26,0
HPS1
68
BPR1
HPS2
68
BPR2
BPE
2,0
HPE
50,0
-
33/72 -
Cut-off in bar
0,02
17,00
-8
0,47
17,00
-9
0,39
1,45
8,18
Interlocking in bar
0,72
13,00
1,17
13,00
1,09
2,1
12,2