Installation • Instalación
Installation • Instalação
1
2 2
3 3
4 4
5 5
wrong • no correcto
incorrect • incorrecto
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1
6
4
5 5
6
correct • correcto
correct • correcto
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1. Feed pipe and fitting at least ½ ! ''
2. No filters in feed line
9
3. Slope in feed line > 1%!
4. Only use ball valves!
5. Operating pressure: min. 12 psig
6. Short pressure hose!
7. For each metre of rising slope in
8. Lay collecting line (min. ½" ) with
8
7
9. Lead discharge pipe from the top
Note: Pressure differences!
Each condensate source must be
drained separately!
Note: Venting!
If the feed line cannot be laid with
sufficient slopeor if there are other
inflow problems, it will be necessary
to install a venting line!
Note: Deflector area!
If drainage is to take place directly
from a line, it is advisable to arrange
the piping so that the air flow is di-
verted.
english
max. 240 psig
the outlet line, the required mini-
mum pressure will increase by 1.5
psig.
The rise of the outlet line must not
exceed 17 feet!
1% of slope.
into collecting line.
BEKOMAT 21, 21 PRO