General electrical data
EMC
Noise emission
Noise immunity
Insulation resistance
Discharge current to PE
(Acc. to EN 61800−5−1)
Enclosure
Protective measures against
Protective insulation of control circuits Protective separation from the mains
1)
EDKCSEE040 DE/EN/FR 5.0
General data and operating conditions
Compliance with the requirements acc. to EN 61800−3
Compliance with the limit class C2 according to EN 61800−3(achieved
with a collective filter typical for the application)
Requirements acc. to EN 61800−3
Requirement
1)
ESD
Conducted high
frequency
RF interference
(housing)
Burst
Surge (surge voltage on
mains cable)
EN 61800−5−1, UL 840: Overvoltage category III
> 3.5 mA AC
IP20 for
Standard installation (built−in unit)
l
Cold−plate technique
l
Mounting with thermal separation (push−through technique), IP54
l
on heatsink side
Short circuit in power terminals (short−circuit−proof at mains
l
connection)
Short circuit in auxiliary circuits
l
– Digital outputs: Short−circuit−proof
– Bus and encoder systems: Limited protection against short circuit
(if necessary, monitoring functions can be switched off, in this
case, error messages must be reset:)
Earth fault (earth−fault protected at mains connection)
l
l
Overvoltage
Double/reinforced insulation acc. to EN 61800−5−1
The noise immunity with the severities given must be ensured by the control cabinet.
The user must check the compliance of the severities given.
l
Technical data
Standard
Severity
EN 61000−4−2
3, i. e.
8 kV for air discharge
l
l
6 kV for contact
discharge
EN 61000−4−6
10 V; 0.15 ... 80 MHz
EN 61000−4−3
3, i. e. 10 V/m;
80 ... 1000 MHz
EN 61000−4−4
3/4, i. e. 2 kV/5 kHz
3, i. e. 1.2/50 ms
EN 61000−4−5
1 kV phase/phase
l
l
2 kV phase/PE
2
69