Assignment of the plug connectors
X4 (CAN)
CH
CL
CG
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type
Impedance
Cable resistance/cross−section
Signal propagation delay
EDKCSEE040 DE/EN/FR 5.0
X14 (CAN−AUX)
Description
CAH
CAN−HIGH
CAL
CAN−LOW
CAG
Reference potential
Cable length £ 300 m £ 70 mW/m / 0.25 … 0.34 mm
Cable length 301 … 1000 m £ 40 mW/m / 0.5 mm
l
Electrical installation
Wiring of system bus (CAN)
Paired with shielding
120 W (95 ... 140 W)
2
(AWG20)
£ 5 ns/m
4
2
(AWG22)
103