1
Convert boiler as per instructions
2
Set (starting, full load, low load) speeds to the correct value (see table)
3
Adjust the boiler to the correct CO
O
/CO
setting values for propane (G31) at low load
2
2
Boiler type
Fan speed (rpm)
Low load,
210- 80 kW
1500
210- 120 kW
1400
Table 1: O
/ CO
setting values for propane (G31) (front housing removed)
2
2
O
/CO
setting values for propane (G31) at full load
2
2
Boiler type
Fan speed (rpm)
Full load,
210- 80 kW
5600
210- 120 kW
6100*
Table 2: O
/ CO
setting values for propane (G31) (front housing removed)
2
2
* USA and Canada max. 5600
Gas inlet pressure
12-20 inches w.c. (30-50mBar)
Manifold pressure
N.A.
Input rating Propane:
80 kW 83 - 304 MBTU
120 kW 83 - 399 MBTU
160 kW 135 - 581 MBTU
200 kW 152 - 701 MBTU
1
3
CO2
CO2
2
level (see table)
2
CO
2
%
10.5
10.5
CO
2
%
10.0
10.0
(24.3 - 89 kW)
(24.3 - 117 kW)
(39.6 - 170 kW)
(44.5 - 205 kW)
6
Control
Setting
O
margin
margin
%
%
%
0.5
0.3
4.9
0.5
0.3
4.9
Control
Setting
O
margin
margin
%
%
%
0.7
n/a
5.7
0.7
n/a
5.7
4
Control margin
2
%
0.8
0.8
Control margin
2
%
1.3
1.3
Setting
margin
%
0.5
0.5
Setting
margin
%
n/a
n/a

Publicité